Specifications

5-28
www.moxa.com
info@moxa.com
Remote Monitoring Solutions
Industrial I/O >
ioLogik W5340
5
Pin Assignment
I/O (left to right)
Ordering Information
Dimensions (unit = mm)
Available Models
ioLogik W5340: Active GPRS I/O device with 4 AIs, 8 DIOs, and 2 relay outputs
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
AI0+
AI0-
AI1+
AI1-
DI_COM1
DIO0
DIO1
DIO2
DIO3
GND
R0_NO
R1_NO
AI2+
AI2-
AI3+
AI3-
DI_COM2
DIO4
DIO5
DIO6
DIO7
GND
R0_C
R1_C
Over-temperature Shutdown: 160°C
Output Current Rating: Max. 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Relay Output
Channels: 2 Form A (N.O.) relay outputs, 5 A
Contact Rating: 5 A @ 30 VDC, 5 A @ 240 VAC, 5 A @ 110 VAC
Inductance Load: 2 A
Resistance Load: 5 A
Breakdown Voltage: 500 VAC
Relay On/Off Time: 10 ms, 5 ms (max.)
Initial Insulation Resistance: 1G min. @ 500 VDC
Expected Life: 100,000 times (Typical)
Initial Contact Resistance: 30 milli-ohms (max.)
Pulse Output: 20 operation times per minutes at rated load
Isolation: 3K VDC or 2K Vrms
Power Requirements
Power Input: 24 VDC nominal, 12 to 36 VDC
Power Consumption:
• GPRS Always On (Communication): 4.2 W
Environmental Limits
Operating Temperature: -10 to 55°C (14 to 131°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Regulatory Approvals
EMI: FCC part 15, CISPR (EN55022) Class A
EMS:
IEC 61000-4-2 (ESD), level 2/3
IEC 61000-4-3 (RS), level 2
IEC 61000-4-4 (EFT), level 2
IEC 61000-4-5 (Surge), level 3
IEC 61000-4-6 (CS), level 2
IEC 61000-4-8 (PM), level 1
IEC 61000-4-11 (DIP)
IEC 61000-6-2 (ESD), level 2/3
IEC 61000-6-4 (EFT), level 2
Safety: UL 508
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Note: Please check Moxa’s website for the most up-to-date
certifi cation status.
Warranty
Warranty Period: 2 years
Details: See www.moxa.com/warranty
135
105
46.8
43.89
Front View Side View
Rear View Top View