Specifications
5-16
www.moxa.com
info@moxa.com
Remote Monitoring Solutions
Industrial I/O >
ioLogik E2212
5
Active Ethernet I/O with 8 digital inputs, 8 digital outputs,
and 4 confi gurable DIO
ioLogik E2212
Selectable digital I/O combination (by software) ›
Accepts PNP or NPN sensors ›
DI counter saved automatically when power shuts off ›
Instant event messaging by TCP/UDP/email/SNMP trap ›
Easy-to-use Click&Go™ Logic for local output control ›
PC-based confi guration utility and web console ›
I/O control over Modbus/TCP and SNMP protocol ›
Windows/WinCE VB/VC.NET and Linux C APIs ›
Peer-to-Peer I/O without controller ›
Specifi cations
Introduction
Flexible Digital Input/Output Confi guration
The ioLogik E2212 provides system integrators with the flexibility to
handle various field demands with channels that can be configured
by software for input or output operation. You can configure the I/O
channels to suit your needs, for combinations such as 12-inputs/8-
outputs, 8-inputs/12-outputs, or 10-inputs/10-outputs.
Single Ethernet DIO that Accepts 3 Sensor Types
Unlike traditional Ethernet I/O products, the ioLogik E2212 can connect
to dry contact, PNP, and NPN sensors at the same time. You can
choose the sensor type based on your wiring approach.
Pin Assignment
I/O (left to right)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DI.COM1
DI0
DI1
DI2
DI3
DI4
DI5
DI.COM2
DI6
DI7
DIO8
DIO9
DIO10
DIO11
GND
DO0
DO1
DO2
DO3
DO4
DO5
DO6
DO7
DO.PWR
Ordering Information
Digital Input
Channels: 8, source/sink selectable
Sensor Type: 2 6-point groups for NPN/PNP type
I/O Mode: DI or Event Counter (up to 900 Hz)
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact: (For Source Type)
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Common Type: 6 points per COM
Isolation: 3K VDC or 2K Vrms
Counter/Frequency: 900 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Over-voltage Protection: 36 VDC
Poweroff Counter Memory: 48 bytes
Digital Output
Channels: 8, sink type, 36 VDC, 200 mA
I/O Mode: DO or Pulse Output (up to 100 Hz)
Pulse Wave Width/Frequency: 10 ms/100 Hz
Over-voltage Protection: 45 VDC
Over-current Limit: 400 mA (typical)
Over-temperature Shutdown: 175°C (min.)
Output Current Rating: Max. 200 mA per channel
Isolation: 2K Vrms or 3K VDC (Magnetic)
DI/DO Confi gurable Channels
Channels: 4
I/O Mode:
• DI or Event Counter (up to 900 Hz)
• DO or Pulse Output (up to 100 Hz)
ioLogik E2212: Active Ethernet I/O, with 8 digital inputs, 8 digital outputs, and 4 DIOs
LDP1602: LCD module with 16 x 2 text display and 5 buttons
The certifi cation logos shown here apply to some or all of the products in this
section. For details, see “Regulatory Approvals” under “Specifi cations” below.