Installation guide
— 14 —
Optical Fiber
Multi
mode
Single
mode, 15
Single
mode, 40
Single
mode, 80
Distance, km 5 15 40 80
Wavelength, nm 1300 1310 1310 1550
Min. TX Output, dBm -20 -15 -5 -5
Max. TX Output, dBm -14 -6 0 0
Sensitivity, dBm -34 to -30 -36 to -32 -36 to -32 -36 to -32
Recommended Diameter
(Core/Cladding) µm
50/125 9/125 9/125 9/125
(1 dB/km,
800 MHz × km)
Power
Input Voltage 12 to 48 VDC, redundant inputs
Input Current @ 24VDC 0.25 A (EDS-305, EDS-305-M, EDS-305-S,
EDS-308)
0.35 A (EDS-308-M, EDS-308-S, EDS-308-MM,
EDS-308-SS)
Connection Removable “6-pin” Terminal Block
Overload Current
Protection
1.1 A (EDS-305, EDS-305-M, EDS-305-S,
EDS-308) 1.6 A (EDS-308-M, EDS-308-S,
EDS-308-MM, EDS-308-SS)
Reverse Polarity
Protection
Present
Mechanical
Casing IP30 protection, metal case
Dimensions 53.6 x 135 x 105 mm (W x H x D)
Weight 0.63 kg
Installation DIN-Rail, Wall Mounting
Environmental
Operating Temperature 0 to 60
o
C (32 to 140
o
F)
-40 to 75
o
C (-40 to 167
o
F) for -T models
Storage Temperature -40 to 85
o
C (-40 to 185
o
F)
Ambient Relative
Humidity 5 to 95% (non-condensing)
Regulatory Approvals
Safety UL60950 (E212360), UL 508, CSA C22.2 No.
60950, EN60950
Hazardous Location UL/cUL Class I, Division 2, Groups A, B, C and D
(E238559)
ATEX Class I, Zone 2, EEx nC IIC (03CA24537)
EMI FCC Part 15, CISPR (EN55022) class A
EMS EN61000-4-2 (ESD), Level 3
EN61000-4-3 (RS), Level 3
EN61000-4-4 (EFT), Level 3
EN61000-4-5 (Surge), Level 3
EN61000-4-6 (CS), Level 3
Shock IEC60068-2-27
Free Fall IEC60068-2-32
Vibration IEC60068-2-6
WARRANTY