User`s guide
Industrial Protocols EtherNet/IP
2-13
Bits 1= Turbo Ring
Bits 2= Turbo Ring v2
Bits 3= Turbo Chain
Bits 4= MSTP
27
Get/Set
Reset Device
USINT (8)
Reboot and reset to default
1: Reboot the device
2: Reset to default
Common Service List
Service
Code
Implementation
Service Name
Description
Class
Instance
0x0E
Get_Attribute_Single
Used to read an object instance attribute
0x10
Set_Attribute_Single
Used to modify an object instance attribute
Electronic Data Sheet (EDS) File
The EDS (Electronic Data Sheet) file contains electronic descriptions of all relevant communication
parameters and objects of an EtherNet/IP device. It is required for RSLogix 5000 to recognize Moxa switch
and its CIP capability.
The list includes the sections which are described in our EDS file.
• [File]
• [Device]
• [Device Classification]
• [Port]
Icon should be 32 * 32 in pixel.
Rockwell RSLogix 5000 Add-On Instructions
(AOI)
The Rockwell RSLogix 5000 Add-On Instructions (AOI) encapsulates Moxa switch supported EtherNet/IP
functions in a common interface logic component. In RSLogix 5000 programming, users could use the AOI
to communicate with Moxa switches and need not know the internal logic.
Our AOI would provide logic of Moxa switch configuration and monitoring by using EtherNet/IP in explicit
messaging and implicit messaging. The AOI also provides some tags for RSLogix 5000/SCADA
programming.
AOI Installation
To install the AOI, you must use Rockwell RSLogix 5000 version 18 or later and Moxa managed Ethernet
switches with firmware version 3.0 or later.
The Five Major Stages of Installing the AOI
1. Add Moxa switch to the I/O configuration tree
2. Import the Add-On Instruction (AOI)
3. Add an instance of the AOI in your application
4. Create and configure tags for the AOI
5. Download the configured AOI to Rockwell PLC
Add Moxa switch to the I/O configuration tree
In order to import the AOI, the first step is to create a new Ethernet Module in RSLogix 5000.