User`s manual
EDS-600 Series User’s Manual Featured Functions
3-37
Enable Ring 1
Setting Description Factory Default
Enabled Enable the Ring 1 settings
Disabled Disable the Ring 1 settings
Not checked
Enable Ring 2*
Setting Description Factory Default
Enabled Enable the Ring 2 settings
Disabled Disable the Ring 2 settings
Not checked
*You should enable both Ring 1 and Ring 2 when using the Dual-Ring architecture.
Set as Master
Setting Description Factory Default
Enabled Select this EDS as Master
Disabled Do not select this EDS as Master
Not checked
Redundant Ports
Setting Description Factory Default
1st Port
Select any port of the EDS to be
one of the redundant ports.
EDS-608: port 2-3
EDS-611: port G2
EDS-616: port 4-3
EDS-619: port G2
2nd Port
Select any port of the EDS to be
one of the redundant ports.
EDS-608: port 2-4
EDS-611: port G3
EDS-616: port 4-4
EDS-619: port G3
NOTE
There are certain restrictions on which ports can be used as ring ports.
1. You may use any two of the non-Gigabit ports as the ring ports; however, the two ring ports
for a particular switch must be on the same module.
2. If you need to use Giga ports as ring ports, you must use the second and third Gigabit ports
(G2 and G3) as the ring ports (but do NOT use G1).
Enable Ring Coupling
Setting Description Factory Default
Enable Select this EDS as Coupler
Disable Do not select this EDS as Coupler
Not checked