EDS-516A Series User’s Manual Featured Functions
3-19
Initial setup of a “Turbo Ring” or “Turbo Ring V2” ring
1. For each switch in the ring, select any two
ports as the redundant ports.
2. Connect redundant ports on neighboring
switches to form the redundant ring.
The user does not need to configure any of the switches as the master to use Turbo Ring or Turbo
Ring V2. If none of the switches in the ring is configured as the master, then the protocol will
automatically assign master status to one of the switches. In fact, the master is only used to
identify which segment in the redundant ring acts as the backup path. In the following subsections,
we explain how the redundant path is selected for rings configured for Turbo Ring, and Turbo
Ring V2.
Determining the Redundant Path of a “Turbo Ring” Ring
In this case, the redundant segment (i.e., the segment that will be blocked during normal operation)
is determined by the number of EDS-516A units that make up the ring, and where the ring master
is located.
“Turbo Ring” rings with an even number of EDS-516A units
Master
If there are 2N EDS-516A units (an even
number) in the “Turbo Ring” ring, then the
backup segment is one of the two segments
connected to the (N+1)st EDS-516A (i.e., the
EDS-516A unit directly opposite the master).