Installation guide

- 13 -
NOTE
You must enable the Turbo Ring function first before using the
DIP switch to activate the Master and Coupler functions.
NOTE
If you do not enable any of the EDS-510E switches to be the Ring
Master, the Turbo Ring protocol will automatically choose the
EDS
-510E with the smallest MAC address range to be the Ring
Master. If you accidentally enable more than one EDS
-
510E to be
the Ring Master, these EDS
-510E switches will auto-
negotiate to
determine which one will be the Ring Master.
LED Indicators
The front panel of the Moxa EDS-510E contains several LED indicators.
The function of each LED is described in the following table:
LED
Color
Status
Description
STATE
Green
On
The system passed the self-diagnosis
test on boot-up and is ready to run.
Blinking
1.
The switch is under reset progress
(1 time/s).
2. Detect ABC-02-USB connect to
the switch (1 time/2s).
Red On
The system failed self-diagnosis on
boot-up.
RAM Test Fail / System Info. Read
Fail / Switch Initial Fail / PTP PHY
Error.
(+ Green MSTR lit on : HW FAIL)
FW Checksum Fail / Uncompress
Fail.
(+ Green Coupler lit on: SW FAIL)
FAULT
Red On
1. The signal contact is open.
2. ABC Loading/Saving Fail.
3. The port being disabled because
of the ingress multicast and
broadcast packets exceed the
ingress rate limit.
4. Incorrect loop connection in a
single switch.
5. Invalid Ring port connection.
PWR1 Amber
On
Power is being supplied to the main
module’s power input PWR1.
Off
Power is not being supplied to the
main module’s power input PWR1.
PWR2 Amber
On
Power is being supplied to the main
module’s power input PWR2.
Off
Power is not being supplied to the
main module’s power input PWR2.
MSTR/
HEAD
Green On
1. The switch is set as the Master of
the Turbo Ring, or as the Head of
the Turbo Chain.
2. POST H.W. Fail (+Stat on and
Fault blinking).