User`s manual
ioLogik R2140 User’s Manual Using ioAdmin
ioLogik R2140 Network I/O Server Configuration
=============================================
Date: 2006/11/2
Time: 08:49:40 AM
[1. Model]
----------
MOD_TYPE=R2140 - RS-485 Remote I/O Server (8AI + 2AO)
MOD_LOC=
MOD_NAME=
[2. I/O Configurations]
-----------------------
AI00=0,(+/-150mV)
AI01=0,(+/-150mV)
AI02=1,(+/-500mV)
AI03=2,(+/-5V)
AI04=3,(+/-10V)
AI05=4,(0-20mA)
AI06=5,(4-20mA)
AI07=0,(+/-150mV)
AO00=0,(0-10V), AO00_PWN=0,(RAW), AO00_SAFE=0,(RAW)
AO01=0,(0-10V), AO01_PWN=0,(RAW), AO01_SAFE=0,(RAW)
[3. Modbus address table]
-------------------------
CHANNEL I/O TYPE MODBUS REFERENCE MODBUS ADDRESS (Dec, Hex)
AI00 Input 30001 0000, 0x0000
AI01 Input 30002 0001, 0x0001
AI02 Input 30003 0002, 0x0002
AI03 Input 30004 0003, 0x0003
AI04 Input 30005 0004, 0x0004
AI05 Input 30006 0005, 0x0005
AI06 Input 30007 0006, 0x0006
AI07 Input 30008 0007, 0x0007
AO00 Output 40001 0000, 0x0000
AO01 Output 40002 0001, 0x0001
<END>
Import System Config
Select this command to reload a configuration that was exported to a text file. You will need to
restart the ioLogik R2140 in order for the new configuration to take effect. This command may be
used to restore a configuration after loading the factory defaults, or to duplicate a configuration to
multiple ioLogik R2140 servers.
The ioLogik R2140 imports information on the model and I/O configuration.
3-12