ioLogik R2140 User’s Manual Using ioAdmin
I/O Configuration Tab (Administrator)
When logged on as an administrator, you may double click on a channel in the I/O Configuration tab
to configure that channel’s settings.
Configuring Analog Input Channels
The ioLogik R2140 is equipped with 8 AI (analog input) channels that can be set individually to
+/-150 mV, +/-500 mV, +/-5V, +/-10V, 0-20 mA, and 4-20 mA.
Configuring Analog Output Channels
The ioLogik R2140 is equipped with 2 AO (analog output) channels that can be set individually to
0-10V, 4-20 mA.
Power On Settings: Use this field to set the initial value for the AO channel when the ioLogik
R2140 is powered on. The Power On Settings field uses raw data values. If you do not know how to
translate the raw data values into real values, use the Test function for assistance.
Safe Status Settings: Use this field to specify how the AO channel responds to a break in RS-485
communication. When the connection is lost for the amount of time specified in the Host
Connection Watchdog, the ioLogik R2140 enters Safe Status, and the AO channel’s Safe Status
settings will go into effect. Note that the Host Connection Watchdog is disabled by default. If the