User`s manual

ioLogik R2140 User’s Manual Using ioAdmin
Configuration File
ioAdmin allows the configuration
of the ioLogik R2140 to be saved
as a file. The file is viewable as
text and can serve
z as a record or backup of
configuration.
z as a template for the
configuration of other servers.
z as a quick reference guide for
you to configure Modbus
drivers in a SCADA system.
The configuration file includes the
following information:
1. Title, file date and time
2. Model information
3. Modbus address table
ioLogik R2140 Network I/O Server Configuration
=============================================
Date: 2006/11/2
Time: 08:49:40 AM
[1. Model]
----------
MOD_TYPE=R2140 - RS-485 Remote I/O Server (8AI + 2AO)
MOD_LOC=
MOD_NAME=
[2. I/O Configurations]
-----------------------
AI00=0,(+/-150mV)
AI01=0,(+/-150mV)
AI02=1,(+/-500mV)
AI03=2,(+/-5V)
AI04=3,(+/-10V)
AI05=4,(0-20mA)
AI06=5,(4-20mA)
AI07=0,(+/-150mV)
AO00=0,(0-10V), AO00_PWN=0,(RAW), AO00_SAFE=0,(RAW)
AO01=0,(0-10V), AO01_PWN=0,(RAW), AO01_SAFE=0,(RAW)
[3. Modbus address table]
-------------------------
CHANNEL I/O TYPE MODBUS REFERENCE MODBUS ADDRESS
(Dec, Hex)
AI00 Input 30001 0000, 0x0000
AI01 Input 30002 0001, 0x0001
AI02 Input 30003 0002, 0x0002
AI03 Input 30004 0003, 0x0003
AI04 Input 30005 0004, 0x0004
AI05 Input 30006 0005, 0x0005
AI06 Input 30007 0006, 0x0006
AI07 Input 30008 0007, 0x0007
AO00 Output 40001 0000, 0x0000
AO01 Output 40002 0001, 0x0001
<END>
3-3