Specifications

ICF-1180I Series
Serial Media Converters >
Serial Media Converters
13-30
www.moxa.com
info@moxa.com
13
Specifications
Technology
Standards:
IEC 61158-2 for PROFIBUS DP
Interface
P1 Port: PROFIBUS DP (DB9 female)
P2 Port: 10/100 Base FX (ST Connector)
Alarm Contact: One relay outputs with current carrying capacity of 1 A
@ 24 VDC; Normal open
LED Indicator: PWR1, PWR2, Ready, P1 Status, P2 Status
DIP Switches:
DIP 1~4 for baudrate setting
DIP 5: Fiber link monitor
DIP 6: Single Ring
DIP 7: Fiber Inverse Function
PROFIBUS Communication
Data rate: 9.6, 19.2, 45.45, 93.75, 187.5, 500, 1.5M, 3M, 6M and 12M
Kbit/s
Auto Baudrate: Yes
Isolation Protection: 2KV
Optical Fiber Side
Point-to-Point Transmission: Half or Full duplex
Ring Transmission: Half duplex
100BaseFX
Multi-Mode Single-Mode
Wavelength
820 nm 1310 nm
TX Output
-12 dBm -8 dBm
RX Sensitivity
-29 dBm -29 dBm
Link Budget
17 dBm 21 dBm
Typical Distance
4 km 45km
Physical Characteristics
Housing: Metal
Mounting: Din-rail
Dimensions: 30.3 x 70 x 115 mm (1.19 x 2.76 x 4.53 in)
Environmental Limits
Operating Temperature:
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
Operating Humidity: 5 to 95% RH
Storage Temperature: -40 to 75°C (-40 to 167°F)
Power Requirements
Input Voltage: 12 to 48 VDC
Connector: Terminal Block
Power Line Protection: Level 3 (2KV) Surge Protection
Over Current Protection: 1.1 A
Standards and Certifications
Safety: UL 60950-1, EN 60950-1
EMC: CE (EN 55022 Class A, EN 55024)(EMI), FCC Part 15 Subpart B
Class A(EMS)
Warranty
Warranty Period: 5 years
Details: See www.moxa.com/warranty
Available Models
ICF-1180I-M-ST: PROFIBUS to fiber converter, multi-mode, ST connector, 0 to 60°C
ICF-1180I-S-ST: PROFIBUS to fiber converter, single-mode, ST connector, 0 to 60°C
ICF-1180I-M-ST-T: PROFIBUS to fiber converter, multi-mode, ST connector, -40 to 75°C
ICF-1180I-S-ST-T: PROFIBUS to fiber converter, single-mode, ST connector, -40 to 75°C
Package Checklist
• ICF-1180I series PROFIBUS to fiber
converter
• Quick installation guide (printed)
• Warranty card
Pin Assignment
Pin# Signal Name
1 N.C.
2 N.C.
3 Profibus D+
4 RTS
5 Signal common
6 5V
7 N.C.
8 Profibus D-
9 N.C.
PROFIBUS Connector (DB9 Female)
1 2 3 4 5
6 7 8 9
Dimensions and Pin Assignment
Unit: mm (inch)
Ordering Information
115 (4.53)
70 (2.76)
12.83 (0.51)
78.8 (3.10)
30.3 (1.19)