User`s manual

Moxa C Programmable RTU Controllers Module Specifications and Wiring
B-2
16-channel Digital Output Module
RM
-2600-T: 16 digital outputs, 24 VDC, sink type, 0.2 A
Outputs er Module:
16 channels, 24 VDC, sink type
Output Impedance:
120m ohms (typical)
Off
-state Resistance: 500K ohms (typical)
Response Time:
100 ms
Over Current Protection:
200 mA per channel
Isolation:
I/O to logic (photocoupler isolation)
Channel
-to-Channel Isolation: 2.5K VDC
Operating Temperature:
-40 to 75°C
Power Consumption:
24 mA @ 24 VDC (typical)
I/O Ca
ble Wire: AWG 14 (2.0 mm x mm) max.
8-channel Analog Input Module, 16-bit Resolution
R
M-3802-T: 8 analog inputs, 4 to 20 mA, 16 bits
Inputs per Module:
8 channels, differential
Input Current Range:
4 to 20 mA
Input Impendence:
120 ohms
Resolution
Range: 16 bits, 0.24 μA/bit
Accuracy:
±0.1%, FSR @ 25°C
±0.3%, FSR @
-40°C, 75°C
Response Time:
100 ms for all channels
Over Current Protection:
200 mA per channel
Isolation:
I/O to logic (photocoupler isolation)
Channel
-to-Channel Isolation: 2.5K VDC
Operating Temperature:
-40 to 75°C
Power Consumption:
30 mA @ 24 VDC (typical)
I/O Cable Wire:
AWG 14 (2.0 mm x mm) max.