User`s manual

Moxa C Programmable RTU Controllers Module Specifications and Wiring
B-3
8-channel Analog Input Module, 16-bit Resolution
RM
-3810-T: 8 analog inputs, 0 to 10 V, 16 bits
Inputs per Module:
8 channels, differential
Input Current Range:
0 to 10 VDC
Input Impendence:
> 10M ohms
Resolution Range: 16 bits, 0.15 μA/bit
Data Format:
16-bit integer (2’s complement)
Accuracy:
±0.1%, FSR @ 25°C
±0.3%, FSR @
-40°C, 75°C
Sampling Rate:
All channels: 12 samples/sec
Per channel: 1.5 samples/sec
Over Current Protection:
200 mA per channel
Isolation
: I/O to logic (photocoupler isolation)
Channel-to-Channel Isolation: 2.5K VDC
Operating Temperature:
-40 to 75°C
Power Consumption:
30 mA @ 24 VDC (typical)
I/O Cable Wire:
AWG 14 (2.0 mm x mm) max.
NOTE
The 9th slot of the ioPAC 8020
-9 series is reserved for future expansion. All I/O modules may only be install
ed
in slot 1 through slot 8.
4-port unmanaged Ethernet Switch Module
16-channel 24 VDC Digital Input Module
KM
-2430-T: 4-port unmanaged Ethernet switch module,
with M12 connector
Standards:
IEEE 802.3 for 10BaseT
IEEE 802.3u for 100BaseT(X)
IEEE 802.3ab for 1000BaseT(X)
IEEE 802.3x for Flow Control
Processing Type:
Store and Forward
Interface:
Front cabling, M12 connector, 10/100BaseT(X) auto
negotiation speed
Operating
Temperature: -40 to 75°C
Power Consumption:
20 mA @ 24 VDC (typical)