Quick Start
QUICK START GUIDE
Of�ice Pro W20
• Moving the unit:
1 2
3
.
4
NEXT PAGE
Refer to the operaon manual and pay aenon to all the warnings and cauons throughout the manual
NOTE: Refer to the operaon manual for details on choosing the installaon site
A) Roll the unit into the space that needs cooling
Unlock the casters and push the MovinCool unit using the side handles to a flat, level
surface and set the casters back to the LOCKED posion.
B) OPTION 1 set up steps
C) OPTION 2 set up steps
• Water Pipe Connecon:
NEXT PAGE
Left Side Handle
Right Side Handle
Installaon Opons
(Based on the Condenser Inlet Water Connecon)
OPTION 1 Water Pipe Connecon: Pipes are field supplied.
Two water pipes with the 1/2 inch NPT male end connecons are
required.
OPTION 2 Garden Hose Connecon: Garden hoses are available as oponal accessory.
Part Number:
GX484009-0920
1) Remove the caps from the female NPT connecons on the right side panel of the
unit.
Note: Small residues of water may drip when the caps are first removed.
2) Apply teflon tape to the male threads on the two pipes.
3) Connect the two water pipes with the male end connecons to the female
connecons on the unit.
WRENCH A
WRENCH B
4) Hold the wrench A ghtly so that the pipe on the unit is not deformed, then
ghten the connector with the wrench B as shown in the figure below.
5) Make sure that water pipes are connected properly, and there is no
water leakage.
•
Garden Hose Connecon:
2) Apply teflon tape to the male threads on the two supplied garden hose adapters.
3) Screw the supplied garden hose adapters to the female NPT connecons on the
unit as shown in the figure below.
4) Connect the oponal water hoses to the garden hose adapters. Hold the hose-
end connector with the wrench B ghtly to prevent hose rotaon. Then ghten
the swivel nut with the wrench A (see figure below).
WRENCH A
WRENCH B
5) Connect the other end of the garden hoses to the water source. Make sure that
the garden hoses are connected properly, and there is no water leakage.
D) Power up the unit:
Note:
Plug the unit and turn it on.
Voltage Requirement: 1 phase, 115V
Recommended Fuse Size: 15 amps
NEMA Plug Configuraon: 5-15
Office Pro W20 unit has two female 1/2 inch NPT (Naonal Pipe Thread) water connecons.
1) Remove the caps from the female NPT connecons on the right side panel of the
unit.
Note: Small residues of water may drip when the caps are first removed.
Entering Water Temperature*: Between 40 °F to 90 °F
Water Pressure: 150 psi (1,034 kPa) or less
*If the entering water temperature is below 68 °F (20 °C) or above 86 °F (30 °C),
adjustment of the unit's water regulang valve seng is required. Please refer
to the operaon manual for details.
WRENCH A
WRENCH B
4) Hold the female NPT connecons on the unit with wrench A and then ghten
garden hose adapters with wrench B (see figure below).