OPERATION MANUAL OFFICE PRO 12 / OFFICE PRO 18 / OFFICE PRO 24 Unit Serial Number Range: 0711XXXX### to Present (From July 2011 to Present) READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE, AND READ ALL SAFEGUARDS SECCIÓN EN ESPAÑOL SECTION EN FRANÇAIS AVAILABLE AT WWW.MOVINCOOL.
SERIAL NUMBER LOCATION AND IDENTIFICATION Nameplate Label COOLING AMPS. WITH PUMP COMPR. OUTPUT REFRIGERANT/TOTAL CHARGE DESIGN PRESSURE LO/HI PART NO./WEIGHT SERIAL NO. Nameplate Label Position Month Year Model Sequential Number © 2013 DENSO PRODUCTS AND SERVICES AMERICAS, INC. All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission of the publisher. DENSO PRODUCTS AND SERVICES AMERICAS, INC.
OPERATION MANUAL OFFICE PRO 12 / OFFICE PRO 18 / OFFICE PRO 24
Table of Contents SERIAL NUMBER LOCATION AND IDENTIFICATION.................................... 2 FOREWORD....................................................................................................... 5 Definition of Terms............................................................................................5 GENERAL WARNINGS & CAUTIONS .............................................................. 6 INVENTORY ...................................................................................
FOREWORD Congratulations on purchasing the MovinCool portable air conditioner. This manual explains how to install and operate the MovinCool Office Pro 12, Office Pro 18, and Office Pro 24 portable air conditioning units. Please read this operation manual thoroughly to familiarize yourself with the features of the unit and to ensure years of reliable operation. You may also find it useful to keep this operation manual on hand for reference.
GENERAL WARNINGS & CAUTIONS 1. All electrical work, if necessary, should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit. All electrical components replaced must be genuine MovinCool parts, purchased from an authorized reseller. 2. The proper electrical outlet for MovinCool units must be equipped with a UL recognized circuit breaker. 3.
INVENTORY After unpacking your MovinCool unit, please check to make sure you have the following items: 1. Office Pro 12 or Office Pro 18 or Office Pro 24 MovinCool Unit (1) 2. Operation Manual/Product Registration (1) Note: If any of these items were not included in the box or appear damaged, please contact your MovinCool reseller for replacement.
INSTALLATION Choosing an Installation Site CAUTION: Following are some precautions to consider before choosing your installation site. Please review carefully as improper installation may result in personal injury or damage to the unit. 1. Do not use the unit in areas where leakage of flammable gas may occur. 2. Do not use the unit in areas where it is exposed to rain or water. 3. Do not use the unit in an environment which contains excessive amounts of corrosive gas or vapour. 4.
INSTALLATION (cont.) Moving the Unit Unlock the casters and push the MovinCool unit using the side handles to a flat, level surface and set the casters back to the LOCKED position.
INSTALLATION (cont.) Plugging in the Unit 1. Check the prongs and surface of the power cord plug for dust/dirt. If dust and/ or dirt are present, wipe off with a clean, dry cloth. 2. Check the power cord, plug and prongs for damage or excess play. If any damage or excess play is found, contact your MovinCool reseller or a qualified technician for repair. WARNING: 1. If the power cord or plug is damaged, replacement should only be performed by qualified electrical personnel. 2.
INSTALLATION (cont.) Plugging in the Unit (cont.) CAUTION: The power source should be a dedicated single outlet circuit with UL recognized short-circuit and ground fault protective breaker. Do not share the AC outlet with any other instrument or equipment. The minimum power supply rating and the maximum fuse size for each corresponding model are listed below.
INSTALLATION (cont.) Warning Signal Connection (Output Signal Terminal L+ and L-) The controller is equipped with a warning signal output relay type (Form C, normal open dry contact) which can be used to monitor the failure condition. Relay contactor is closed when the following condition has occurred: a. Tank full b. Temperature sensor fails c.
INSTALLATION (cont.) Fire Alarm Control Panel Connection (Input Signal Terminal E+ and E-) The controller is equipped with a normal open input signal connection, which can be connected directly from the fire alarm control panel. This input signal terminal should only be connected to a close or open dry contact signal. When receiving the signal from the fire alarm control panel, the unit turns off and does not turn back on until it has been RESET. Connecting Fire Alarm Control Panel to Controller 1.
INSTALLATION (cont.) LCDI Power Cord Instruction WARNING The LCDI device is a non-serviceable device. Attempting to open the device may expose the user to the hazards of electric shock, and could void warranties of this product. Manufacturer’s reliability is limited to the replacement of the device. CAUTION 1. 2. 3. 4. 5. 6. 7. 8. Read the attention printed on the device for proper use and handling of this device. This device is used for monitoring leakage current. Do not immerse in water.
FEATURES For all models: 1. A digital electronic control panel, which allows the user to easily control the unit’s operation. 2. Dual fan speeds (either HIGH or LOW) in both COOL and FAN ONLY modes. 3. Digital LCD display with blue backlight that indicates: a. Clock with day and time b. Room temperature and set point temperature (either Fahrenheit or Celsius) c. Fan speed status d. Cool mode status e. Program start time and stop time f. Program run and stop g. Status codes h. Keypad lock 4.
OPERATION Control Panel Before operating the unit, it is important to familiarize yourself with the basic controls located on the control panel. 1. COOL Mode Button Activates/deactivates the COOL mode/turns the unit off. 2. FAN Mode Button Activates/deactivates the high, low, and off fan speed. 3. SET TEMP Buttons ( / ) Temperature scale illuminates to indicate the current LED temperatures being displayed are either in °C or °F; also displays the clock when programming. 4.
OPERATION (cont.) Control Panel (cont.) LCD Indicators 9. MO...SU Illuminates to indicate selected day of the week. 10. °C or °F Temperature displayed in either Fahrenheit or Celsius (see Note). 11. AM/PM Illuminates to indicate AM or PM time of day. 12. PROGRAM Blinking during program editing mode. 13. PROGRAM ON Illuminates to indicate program is running. 14. START Illuminates to indicate program start time. 15. STOP Illuminates to indicate program stop time. 16.
OPERATION (cont.) Operating Modes The Office Pro 12, Office Pro 18, and Office Pro 24 can be operated in two modes, FAN ONLY and COOL. When in FAN ONLY mode, the unit circulates the surrounding air. When in COOL mode, the compressor is operated and cool air is circulated. 1. COOL Mode Once the compressor has been disengaged for more than 120 seconds, the unit operates in FAN ONLY mode for approximately 5 seconds before the compressor re-engages. 2.
OPERATION (cont.) Set Clock Prior to operating the Office Pro 12, Office Pro 18, or Office Pro 24 users should set the clock of the controller to the correct time as shown in the following steps: 1. Press and hold the SET CLOCK button for 3 seconds or until beep. (LCD indicates blinking “CLOCK” and blinking “day of the week”.) 2. Press SET TEMP buttons to scroll day of the week. Step 1 & 6 3. Press ENTER button. Step 2 to 5 4. Press SET TEMP buttons to select correct hour. 5. Press ENTER button. 6.
OPERATION (cont.) Operating in FAN ONLY Mode 1. The unit can also be operated in FAN ONLY mode by pressing FAN HI/LO button (LCD indicates “FAN HI/LO” and “COOL OFF”). 2. The unit can then be turned off by pressing the FAN HI/LO button until fan turns off (FAN ONLY mode speed sequences are HI→LO→OFF). Changing from FAN ONLY Mode to COOL Mode The COOL mode can be activated while the unit is operating in FAN ONLY mode. To do this, simply press the COOL ON/OFF button (LCD indicates “COOL ON”).
OPERATION (cont.) How to Set a Program SET START TIME 1. Press and hold the SET PROG button for 3 seconds or until beep. 2. Press SET TEMP buttons to scroll day of the week. 3. Press ENTER button. 4. Press SET TEMP buttons to select desired hour. 5. Press ENTER button. 6. Press SET TEMP buttons to select desired minute. 7. Press ENTER button. SET STOP TIME 8. Press SET TEMP buttons to scroll day of the week. 9. Press ENTER button. 10. Press SET TEMP buttons to select desired hour. 11. Press ENTER button.
OPERATION (cont.) How to View and Delete Program 1. Press and hold the SET PROG button for 3 seconds or until beep. 2. To view edited program - While pressing and holding the SET PROG button, press SET TEMP buttons ( / ) to scroll program sequence. 3. To delete a program - Press ENTER and SET PROG buttons once simultaneously. 4. To delete multiple program - Press and hold ENTER and SET PROG buttons simultaneously. How to Run and Stop Program 1.
OPERATION (cont.) Self-Diagnostic Codes Self-diagnostic codes are displayed on the control board under the following conditions. LCD Display Codes Condition When the drain tank switch shuts off the unit, LCD displays “TANK FL” and “TANK FULL” LED flashes. Once emptying the drain tank procedure is completed and ON/OFF has been pushed, unit returns to normal operation.
OPERATION (cont.) Empty the Drain Tank During COOL mode, condensate water accumulates in the drain tank. When the drain tank becomes full, the “TANK FULL” LED flashes and the LCD displays “TANK FL” and the unit turns off automatically. Note: If you want to empty the drain tank, while the unit is in operation, press the COOL ON/OFF button to turn the unit off. If a program is running, you must first stop the program by pressing the RUN/STOP button. 1. Open the drain tank door. 2.
OPERATION (cont.) Condensate Pump Kit (Optional) A condensate pump kits are available to allow continuous operation and to eliminate the need for a drain tank. When the water collects to level (A) in the pump reservoir, the condensate pump begins to operate and discharge the water. Note: The compressor does not operate while the condensate pump is discharging the water for the Office Pro 12 and Office Pro 18.
DAILY INSPECTION & MAINTENANCE Empty the Drain Tank To empty the drain tank, refer to instructions on page 24. Clean the Air Filters Clean the air filters once a week. If the unit is used in a dusty environment, more frequent cleaning may be required. A dirty air filter can reduce air output resulting in a decrease in the cooling capacity. Filter Removal Method 1. Turn the unit off by pressing the COOL ON/OFF button. If a program is running, you must first press the PROGRAM RUN button. 2.
DAILY INSPECTION & MAINTENANCE (cont.) In-Season/Off-Season Inspection & Maintenance In-Season WARNING: To prevent an accident due to electrical shock, perform inspection and maintenance only after unplugging the power cord. 1. Check the prongs and surface of the power cord plug for dust and/or dirt. If dust and/or dirt are present, wipe off with a clean dry cloth. 2. Check the power cord, plug and prongs for damage or excess play.
TROUBLESHOOTING Check the following items before calling your MovinCool reseller or a qualified technician. CONDITION Unit does not operate. Insufficient cooling. POSSIBLE CAUSE REMEDY 1. Ground fault breaker trip or LCDI power cord trip. Reset breaker or reset power cord. 2. Drain tank is full. (“TANK FULL” LED flashes.) Empty the drain tank. 3. High pressure switch activated 10 times in 24 hours. 1. Clean air filter. 2.
TECHNICAL SPECIFICATIONS ..
TECHNICAL SPECIFICATIONS (cont.) ITEMS/FEATURES Operating Conditions Inlet air: Maximum Minimum Control Device Temperature control Programmable timer Two speed fan Office Pro 12 Office Pro 18 Office Pro 24 95°F(35°C), 60%RH 65°F(18.3°C), 50%RH 95°F(35°C), 60%RH 65°F(18.3°C), 50%RH 95°F(35°C), 60%RH 65°F(18.
WARRANTY STATEMENT DENSO PRODUCTS AND SERVICES AMERICAS, INC. ("DENSO") warrants its MOVINCOOL Products only to the extent stated in its official written warranties.
P/N: 484007-3582EN Third Issue: April 2013