6.2.9. Serial communication parameters
F09
Range
Default
Ser.
081
Serial device address (unit number)
11 … 99
11
90
082
Serial baud rate
0 … 6
0
91
0=
9600 Baud
1=
4800 Baud
2=
2400 Baud
3=
1200 Baud
4=
600 Baud
5=
19200 Baud
6=
38400 Baud
083
Serial data format
0 … 9
0
92
0=
7 Data, Parity even, 1 Stop
1=
7 Data, Parity even, 2 Stop
2=
7 Data, Parity odd, 1 Stop
3=
7 Data, Parity odd, 2 Stop
4=
7 Data, no Parity, 1 Stop
5=
7 Data, no Parity, 2 Stop
6=
8 Data, Parity even, 1 Stop
7=
8 Data, Parity odd, 1 Stop
8=
8 Data, no Parity, 1 Stop
9=
8 Data, no Parity, 2 Stop
084
Serial protocol select *)
0 … 1
1
H1
0=
Transmission = Unit Nr. Data, LF, CR
1=
Transmission = Data, LF, CR
085
Serial timer (sec.) for timer transmissions *)
0.000 … 99.999
0
H2
086
Serial register code of the transmit parameter *)
0 … 19
14
H3
*) for more details please see appendix in section 8
6.2.10. Switching characteristics and presets
F10
Range
Default
Ser.
089
Pulse time (sec.) output K1 (0 = static output)
0.00 … 9.99
0.00
H6
090
Pulse time (sec.) output K2 (0 = static output)
H7
091
Pulse time (sec.) output K3 (0 = static output)
H8
092
Pulse time (sec.) output K4 (0 = static output)
H9
093
Switching hysteresis K1 (display units) *)
0 … 9999
0
I0
094
Switching hysteresis K2 (display units) *)
I1
095
Switching hysteresis K3 (display units) *)
I2
096
Switching hysteresis K4 (display units) *)
I3
*) The switching point equals to the preset value and the return point is displaced by the hysteresis setting