ZD34007c_e.doc / Nov-15 Page 33 / 50
F06
(continued)
Range
Default
Ser.
053
Switching characteristics of input „Cont.1“
0 … 7
0
E3
0=
NPN (switch to -) function active LOW
1=
NPN (switch to -) function active HIGH
2=
NPN (switch to -) rising edge
3=
NPN (switch to -) falling edge
4=
PNP (switch to +), function active LOW
5=
PNP (switch to +), function active HIGH
6=
PNP (switch to +), rising edge
7=
PNP (switch to +), falling edge
054
Function assignment to input „Cont.1“
0 … 14
0
E4
0=
No function
1=
Reset counter 1 (encoder 1) and read **)
(Clears also points of change of direction)
2=
Reset counter 2 (encoder 2) and read **)
3=
Reset counter 1 and counter 2 and read **)
4=
Set counter 1 to Set Value 1 *)
5=
Set counter 2 to Set Value 2 *)
6=
Set both counters to Set Value *)
7=
Inhibit counter 1 and read **)
8=
Inhibit counter 2 and read **)
9=
Read only **)
10=
Start serial transmission
11=
Reset minimum/maximum records
12=
Scroll actual display
13=
Special command (depends on counter mode)
14=
Hardware keypad interlock
055
Switching characteristics of input „Cont.2“
0 … 7
0
E5
See „Cont.1“ (F06.053)
056
Function assignment to input „Cont.2“
0 … 14
0
E6
See „Cont.1“ (F06.054)
057
Switching characteristics of input „Cont.3“
0 … 7
0
E7
See „Cont.1“ (F06.053)
058
Function assignment to input „Cont.3“
0 … 14
0
E8
See „Cont.1“ (F06.054)
059
Switching characteristics of input „Cont.4“
0 ... 3
0
E9
0 =
1 =
2 =
3 =
= NPN (switch to -), active LOW
= NPN (switch to -), active HIGH
= PNP (switch to +), active LOW
= PNP (switch to +), active HIGH
static switching
functions only
060
Function assignment to input „Cont.4“
0 … 14
0
F0
See „Cont.1“ (F06.054)
Unconnected NPN inputs are always HIGH (internal pull-up resistor)
Unconnected PNP inputs are always LOW (internal pull-down resistor)
*) Parameter F10.101 defines the source of the Set Value (see 6.3)
**) “Read” refers to models 6xx with thumbwheel switches only. See appendix.