Switching Menu (switching characteristics of the relays/outputs)
Code
Range
Default
Relay Action (for more details see section 9.3)
Selection of the relays/transistor outputs of which the switching state should
be overridden by key command or remote command (non-selected relays will
continue normally)
„K8“
0…8
0
0
No relay/transistor output selected
1
Relay 1/transistor output 1
2
Relay 2/transistor output 2
3
Relays 1 & 2/transistor output 1&2
4
Relay 3/transistor output 3
5
Relays 1 & 3 /transistor output 1&3
6
Relays 2 & 3/transistor output 2&3
7
All relays/transistor outputs selected
8
Freeze actual switching state of all relays/transistor outputs
Action Polarity (for more details see section 9.3)
Desired override state of the corresponding relays/transistor outputs
(parameter is out of function when “Relay Action” is set to “8”)
„K9“
0…7
0
Setting
Relay/out K1
Relay/out K2
Relay/out K3
0
0
0
0
1
1
0
0
2
0
1
0
3
1
1
0
4
0
0
1
5
1
0
1
6
0
1
1
7
1
1
1
0 = Coil of the relay is de-energized transistor output off.
1 = Coil of the relay is energized transistor output on