Instructions

Ax350_06a_oi_e.docx / Aug-19 page 38 / 78
Continuation „Serial Menu”:
SERIAL PROTOCOL
Determines the sequence of characters send, when using the serial output for cyclic data transmission under
time control (xxxxxxx = value SERIAL VALUE).
Setting „1“ removes the unit address from the string which allows a slight faster transmission cycle.
0
Transmission report = Unit Nr., +/-, data, LF, CR
1
1
+/-
X
X
X
X
X
X
X
LF
CR
1
Transmission report = +/-, data, LF, CR
+/-
X
X
X
X
X
X
X
LF
CR
SERIAL TIMER (S)
This register determines the cycle time in seconds for cycling transmission of SERIAL VALUE when using the serial
output. (On a serial request, the cycling transmission is stopped for 20 s)
0.000
All cyclic transmission is switched off. The unit will send data upon a serial request or
with command SERIAL PRINT.
60.000
Cycle time in seconds.
SERIAL VALUE
This parameter defines the value to be transmitted.
Setting
Code
Register contents
0
:0
Value input 1
1
:1
Value input 2
2
:2
Result of the linking of input1 and input 2
3
:3
Result totalizator 1
4
:4
Result totalizator 2
5
:5
Result of the linking of 1 and 2 with totalization
6
:6
Minimum value input 1
7
:7
Maximum value input 1
8
:8
Minimum value input 2
9
:9
Maximum value input 2
MODBUS
This parameter enables the Modbus protocol and determines the Modbus address.
For details of the Modbus communication please refer to the additional manual Modbus_RTU
0
Modbus disabled
Serial interface is using Lecom protocol (Motrona default protocol)
1 … 247
Modbus enabled: Serial interface is using Modbus RTU protocol
The set value is the Modbus address of the device.