Operating Manual touchMATRIX® Indicator AX350 Process indicator with two 16 bit analog inputs, touch screen and graphic display Product Features: Operating modes for visualization of input 1, input 2 or combinations of inputs (1+2, 1-2, 1x2, 1:2) Two universal 16 bit analog inputs for -10 … +10 V / 0 … 10 V / 0 … 20 mA / 4 … 20 mA High accuracy reference output 10 V for potentiometers > 1 kOhm Bright and high-contrast display with event-dependent color variations Emulation of a 7-segment display inclu
Version: AX350_01a_oi/cn/Jan-17 AX350_02a_oi/cn/Feb-17 AX350_02b_oi/cn/March-17 AX350_02c_oi/cn/Jul-17 AX350_3a_oi/cn/Okt-17 AX350_4a_oi/sn/April-18 AX350_5a_oi/cn/June-18 AX350_5b_oi/cn/July-18 AX350_6a_oi/tgo/March-19 Description First Version Second Version minor changes and fixes minor changes and fixes Expansion of the scale units Extension with IO-link Extension with Modbus With Modbus and IO-Link description Extension of large display Legal notices: All contents included in this manual are protect
Table of Contents Safety Instructions and Responsibility.......................................................................... 4 General Safety Instructions ............................................................................................................. 4 Use according to the intended purpose .......................................................................................... 5 Installation ...............................................................................................
Parameter setting ................................................................................................................................... 47 Modbus Communication ......................................................................................................................... 48 Diagnostics ............................................................................................................................................. 50 IO-Link Modul ..........................................
Use according to the intended purpose The unit is intended exclusively for use in industrial machines, constructions and systems. Nonconforming usage does not correspond to the provisions and lies within the sole responsibility of the user. The manufacturer is not liable for damages which have arisen through unsuitable and improper use. Please note that device may only be installed in proper form and used in a technically perfect condition (in accordance to the Technical Specifications).
Installation The device is only allowed to be installed and operated within the permissible temperature range. Please ensure an adequate ventilation and avoid all direct contact between the device and hot or aggressive gases and liquids. Before installation or maintenance, the unit must be disconnected from all voltage-sources. Further it must be ensured that no danger can arise by touching the disconnected voltage-sources.
Introduction This series of display unit is suitable for analog signals (-10 … 10V or 0/4 … 20 mA). It is very versatile in use, due to the intuitive handling and the extensive range of functions and options. Operation mode All functions are can be configured in the parameter menu.
Function diagram Ax350_06a_oi_e.
Electrical Connections The terminal screws should be tightened with a slotted screwdriver (blade width 2mm). DC Power Supply The unit accepts DC supply from 18 to 30 V at the terminals 1 and 2. The power consumption depends on the level of the supply voltage with aprox. 100 mA and the additional current required at the auxiliary voltage output. All GND terminals are internally interconnected. Auxiliary Voltage Output Terminal 3 and 4 provide an auxiliary output for supply of sensors and encoders.
Analog Input The reference potential (AGND) for the analog inputs is connected at terminal 5. The unit provides two 16 bit analog inputs at terminal 6 and 7. The characteristics of the analog inputs (voltage input or current input ) can be set in the Menu IN 1/IN 2 PROPERTIES.
Control Inputs The three control inputs at terminal 10, 11 and 12 have HTL PNP characteristics. In the COMMAND MENU the programmable functions for the control inputs can be assigned. Available functions are: reset the display value, display switching, locking the touch screen or release the lock function of the control or relay outputs. Wiring of the control inputs: Unconnected control inputs are always “LOW”. All inputs are designed to receive impulses from an electronic impulse source.
Serial interface (Option AO/AR/CO/CR) A serial interface (RS232 or RS485) is available at terminal 16, 17 und 18. This interface can be configured in the SERIAL MENU.
Wiring of the control-outputs: AC Power supply (Option AC) The unit accepts AC supply from 115 to 230 V at the terminals 24 and 25. The power consumption depends on the level of the supply voltage with aprox. 3VA and the additional current required at the auxiliary voltage output. Devices with option AC can also be supplied with a DC voltage between 18 and 30 VDC at terminals 1 and 2.
IO-Link (Option IO) An interface for connecting to an IO-Link master is available at terminal 34, 35 and 36. The display device (IO-link device) must always be connected to a separate power supply (AC or DC). The display device (IO-link device) can be operated in two ways. Display of 2 output process data (8 bytes): 2 output process data are sent by the IO-Link master cyclically. The two values can be parameterized or scaled in the Menu IO-LINK PROPERTIES.
Operation and touch screen Screen structure for parametrization The parameter menus and the parameters are described in chapter 5. Start setup procedure: To edit the parameters, press the touchscreen for 3 seconds. Menu selection: Select the parameter menu via arrow buttons and confirm with “OK”. The menu selection can be terminated with „C“. Parameter selection: Select the parameter via arrow buttons and confirm with „OK“. The parameter selection can be terminated with „C“.
Screen structure in operation The following screens are available during operation. Depending on the device version and the selected operation mode, not all displays will be shown. The source (IN1, IN2, …) for the single channel display, the two channel display and the large display are defined in the DISPLAY MENU. Single line display with unit and status bar To switch to the next display, press the touch screen. Control - or Relay status are only shown with Option AO, CO, RL.
Continuation “Screen structure in operation”: Display for quick start for enter preselection values (PRESELECTION VALUES) To switch to the next display, press the top of the screen or the “skip” button. This is only possible with Option AO, CO, RL Display with actual / minimum / maximum values of input 1 and input 2 To switch to the next display, type on the touch screen.
Continuation “Error messages”: ERROR: MAX. TOP DISPLAY VALUE Top display value of the two-line display is greater than +99 999 999 ERROR: MIN. TOP DISPLAY VALUE Top display value of the two-line display is less than -99 999 999 ERROR: MAX. DOWN DISPLAY VALUE Down display value of the two-line display is greater than +99 999 999 ERROR: MIN. DOWN DISPLAY VALUE Down display value of the two-line display is less than -99 999 999 ERROR: MAX.
Continuation “Error messages”: ERROR: MIN. LARGE DISPLAY VALUE The display value of the large display is less than - 999 The error messages described are automatically reset as soon as the corresponding display value is within the representable range. Ax350_06a_oi_e.
Parameter / Overview-Menu Structure This section provides an overview of the menus and their parameters. The menu names are printed bold and the associated parameters are listed under the menu name. Depending on the device version and the selected operation mode, only the necessary menus / parameters are shown.
Menu / Parameter IO LINK PROPERTIES IN1 FACTOR IN1 DIVIDER IN1 ADDITIVE VALUE IN1 DECIMAL POINT IN1 SCALE UNITS IN2 FACTOR IN2 DIVIDER IN2 ADDITIVE VALUE IN2 DECIMAL POINT IN2 SCALE UNITS PRESELECTION VALUES PRESELECTION 1 PRESELECTION 2 PRESELECTION 3 PRESELECTION 4 PRESELECTION 1 MENU SOURCE 1 MODE 1 HYSTERESIS 1 PULSE TIME 1 OUTPUT TARGET 1 OUTPUT POLARITY 1 OUTPUT LOCK 1 START UP DELAY 1 EVENT COLOR 1 PRESELECTION 2 MENU SOURCE 2 MODE 2 HYSTERESIS 2 PULSE TIME 2 OUTPUT TARGET 2 OUTPUT POLARITY 2 OUTPUT
General Menu OPERATIONAL MODE This parameter specifies the selected measuring function..
IN 1 Properties This menu defines the parameter for input 1. CONFIGURATION This parameter defines the configuration of input 1. 0 1 2 -10 … 10 V 0 … 20 MA 4 … 20 MA -10 … 10 V 0 … 20 mA 4 … 20 mA START VALUE This parameter defines the display value of an input signal of 0V, 0mA or 4mA. Signal values between START VALUE and END VALUE behave proportional.
Continuation “IN 1 Properties”: SAMPLING TIME (S) The configured value corresponds to the sampling interval. This time interval in seconds defines the time between the single samples of the analog signals. This parameter directly affects the response time of the unit. 0,001 Shortest sampling time 0,01 60,000 Default value Longest sampling time AVERAGE FILTER Selectable average filter function to avoid measuring fluctuations.
IN 1 Linearization The linearization points of input 1 are defined in this menu. This menu is shown only, if the linearization is selected in 1 PROPERTIES. Linearization description and examples are shown in the appendix. P1(X) … P24(X) X-coordinate of the linearization point. This value representing the display value which the unit show in the display without linearization.
IN 1 Totalization The totalization function is defined in this menu. This menu will only be showed, if the totalization is active in Menu IN 1 PROPERTIES. The totalizator depends on the operation mode. See in the following list.
IN 2 Properties This menu defines the parameter for input 2.
IN 2 Linearization The linearization points of input 2 are defined in this menu. P1(X) … P24(X) X-coordinate of the linearization point, see IN 1Linearization. P1(Y) … P24(Y) Y-coordinate of the linearization point, see IN 1Linearization. IN 2 Totalization The totalization function is defined in this menu. TIME BASE The time base of the totalization, see IN 1 Totalization DIVIDER The devisor for the totalization, see IN 1 Totalization.
Linkage Properties In this menu the parameters for the linked operation mode are defined. This menu is shown only, if in GENERAL MENU an operation mode (z.B. IN1 – IN2) with link was selected. The parameters in Menu IN 1 PROPERTIES and IN 2 PROPERTIES have to be set, before using a linked operation mode. The result of the link can be scaled with the following parameters. FACTOR This parameter defines the factor, the result of the link will be charged.
IO-Link Properties This menu defines the parameters for the display of the two output process data. This menu is only displayed if the device is equipped with the option IO (IO-Link Modul). IN1 FACTOR (Multiplication factor) This parameter defines the factor the received value is multiplied with. -99999999 Smallest value 1 Default value 99999999 Highest end value IN1 DIVIDER (Dividing factor) This parameter defines the factor the received value is devided by.
Preselection Values This menu is used to set the preselection values or the switching points. The preselection values / switching points are always referred to the display value. This menu is only available for devices with option CO, A0 or RL.
Continuation „Preselection 1 Menu“: The totalization depends on the operation mode. See chart in chapter IN 1 Totalization. MODE 1 Switching conditions for preselection 1.
Continuation „Preselection 1 Menu“: PULSE TIME 1 (S) Duration of output pulse for the switching condition of preselection 1 No output pulse (static signal) 0,000 … 60,000 Pulse duration of 60 seconds OUTPUT TARGET 1 Assignment of an output or relay for the switching condition of preselection 1. If more than one switching condition is assigned to one output / relay, the output is set when at least one switching condition is true 0 NO No assignment 1 CTRL OUT 1 Switching condition assigned to “Ctrl.
Preselection 2 Menu SOURCE 2 The reference source for PRESELECTION 2, see PRESELECTION 1 MENU MODE 2 Switching conditions for preselection 2, see PRESELECTION 1 MENU (expect trailing preselection) 6 RES>=PRES-TRAIL See chapter PRESELECTION 1 MENU Trailing preselection 2: Display value is greater or equal to PRESELECTION 1 – PRESELECTION 2 PRESELECTION 2 is the trailing preselection from PRESELECTION 1.
Preselection 3 Menu SOURCE 3 The reference source for PRESELECTION 3, see PRESELECTION 1 MENU MODE 3 Switching conditions for preselection 3, see PRESELECTION 1 MENU (expect trailing preselection) 6 RES>=PRESTRAIL See chapter PRESELECTION 1 MENU Trailing preselection 3: Display value is greater or equal to PRESELECTION 4 – PRESELECTION 3 PRESELECTION 3 is the trailing preselection from PRESELECTION 4.
Preselection 4 Menu SOURCE 4 The reference source for PRESELECTION 4, see PRESELECTION 1 MENU MODE 4 Switching conditions for preselection 4, see PRESELECTION 1 MENU (expect trailing preselection) 6 RES>=PRESTRAIL See chapter PRESELECTION 1 MENU Trailing preselection 4: Display value is greater or equal to PRESELECTION 3 – PRESELECTION 4 PRESELECTION 4 is the trailing preselection from PRESELECTION 3.
Serial Menu This menu defines the basic settings of serial interface. This function is only available for devices with option CO or A0 UNIT NUMMER This parameter defines serial device addresses. The addresses between 11 and 99 can be assigned to the devices. Addresses with zero are not allowed, there are used as broadcast addresses.
Continuation „Serial Menu”: SERIAL PROTOCOL Determines the sequence of characters send, when using the serial output for cyclic data transmission under time control (xxxxxxx = value SERIAL VALUE). Setting „1“ removes the unit address from the string which allows a slight faster transmission cycle. 0 1 Transmission report = Unit Nr.
Analog Out Menu This menu defines the basic settings of the analog output. This function is only available for devices with option A0.
Continuation „Analog Out Menu“: ANALOG GAIN (%) This parameter specifies the maximum conversion of the analog output in %. e. g. 102.00 corresponds to a conversion of 10.2 V or 20.4 mA, when the ANALOG END value is reached. e. g. 95.00 corresponds to a conversion of 9.5 V or 18 mA, when the ANALOG END value is reached.. Smallest gain 0,00 100,00 110,00 Default value Highest gain ANALOG OFFSET (%) This parameter defines the zero offset of the analog output. z. B. 0.20 result in an offset of 0.02 V or 0.
Command Menu INPUT 1 ACTION This parameter defines the function of the input “Ctrl. In 1”. 0 1 2 NO TARA INPUT 1 TARA INPUT 2 3 TARA INPUT 1+2 4 5 RESET TOTAL 1 RESET TOTAL 2 6 RESET TOTAL 1+2 7 8 9 10 11 12 13 14 15 16 TEACH PRESEL. 1 TEACH PRESEL. 2 TEACH PRESEL. 3 TEACH PRESEL.
Continuation „Command Menu”: INPUT 1 CONFIG This parameter defines the switching characteristics of the input “Ctrl. In 1”. 0 ACTIVE LOW Active at „LOW“ (static) 1 ACTIVE HIGH Active at „HIGH“ (static) 2 RISING EDGE Activate at rising edge (dynamic) 3 FALLING EDGE Activate at falling edge (dynamic) INPUT 2 ACTION This parameter defines the function of the input “Ctrl. In 2”. See parameter INPUT 1 ACTION INPUT 2 CONFIG This parameter defines the switching characteristics of the input “Ctrl. In 2”.
Continuation „Display Menu:“ SOURCE SINGLE (Reference source for single-line display) 0 1 2 3 4 5 6 7 8 9 10 11 INPUT 1 INPUT 2 LINKAGE 1 – 2 INPUT 1 TOTAL INPUT 2 TOTAL the reference source is input 1 the reference source is input 2 the reference source is the result of the linking of input1 and input 2 the reference source is input 1 with totalization the reference source is input 2 with totalization the reference source is the result of the linking of input1 and input 2 with LINKAGE TOTAL totalization
Continuation „Display Menu:“ SOURCE DUAL DOWN (Reference source for two-line display, second line) 0 1 2 3 4 INPUT 1 INPUT 2 LINKAGE 1 – 2 INPUT 1 TOTAL INPUT 2 TOTAL 5 LINKAGE TOTAL 6 7 8 9 10 11 IO LINK VALUE 1 IO LINK VALUE 2 MINIMUM VALUE 1 MAXIMUM VALUE 1 MINIMUM VALUE 2 MAXIMUM VALUE 2 the reference source is input 1 the reference source is input 2 the reference source is the result of the linking of input1 and input 2 the reference source is input 1 with totalization the reference source is inp
Continuation „Display Menu:“ COLOR This parameter defines the display color. Event-depending change of the display color by a switching condition is possible (see PRESELECTION 1…4 MENU) Event-depending changes are only available for devices with option CO350, A0350 or RL350. 0 RED Red display 1 GREEN Green display 2 YELLOW Yellow display BRIGHTNESS (%) This parameter defines the brightness of the display in percent Min. brightness 10 Default value 80 Max.
Appendix Data readout via serial interface All codes shown in the parameter SERIAL VALUE are available for serial readout by PC or PLC. The communication of Motrona devices is based on the Drivecom protocol according to ISO 1745 or the Modbus RTU protocol. All protocol details can be found in our manual SERPRO (Drivecom) which is available for download from our homepage www.motrona.com and in the capter “Modbus RTU Interface” in this manual.
Modbus RTU Interface The Modbus interface of the touchMatrix series is a standard Modbus RTU Slave and provides the following Modbus functions: Read Coils Write Single Coil Read Holding Registers Write Multiple Registers Diagnosis For the operation of the interface module and the understanding of this manual basic knowledge in Modbus RTU communication is presupposed.
Continutation “Parameter setting” SERIAL INIT Not valid for Modbus communication SERIAL PROTOCOL Not valid for Modbus communication SERIAL TIMER (S) Not valid for Modbus communication SERIAL VALUE Not valid for Modbus communication MODBUS This parameter enables the Modbus protocol and determines the Modbus address. 0 1 … 247 Do not use for Modbus protocol (Modbus disabled) Modbus enabled: Serial interface is using Modbus RTU protocol The number set here determines the Modbus node address.
Access to actual data Holding Register 0x1000 / 0x1001 hex and following allow access to variables of the device (actual data registers): Holding Register 0x1000 / 0x1001 hex Actual data with serial Code “:0” (Display value) Holding Register 0x1002 / 0x1003 hex Actual data with serial Code “:1” Holding Register 0x1004 / 0x1005 hex Actual data with serial Code “:2” Holding Register 0x1006 / 0x1007 hex Actual data with serial Code “:3” etc.
Diagnostics The device supports the diagnostics subfunction 00 “Return Query Data”. Other diagnostics functions are not available. IO-Link Modul This document is an additional description of the device AX350 with the option IO. A device with this additional option is required to use this device description. It contains important notes and information regarding IO-link communication data.
3 (L-) 4 (C/Q) Ax350_06a_oi_e.
Parameter data ISDU Index DPP1 Index 7 8 9 10 11 Name of the Parameter Length in bytes IDENTIFICATION MENU Access Default Value Range VendorID R 2 980 / 0x 03D4 - Device ID R 3 1265670 / 0x 135006 - 16 17 18 19 Vendor Name Vendor Text Product Name Product ID R R R R 12 21 11 5 - 20 Product Text R 35 21 22 23 24 Serial Number Hardware Revision Firmware Revision Application Specific Tag motrona GmbH http://www.motrona.
ISDU Index 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 DPP1 Index Name of the Parameter IN1 LIN P1(X) IN1 LIN P1(Y) IN1 LIN P2(X) IN1 LIN P2(Y) IN1 LIN P3(X) IN1 LIN P3(Y) IN1 LIN P4(X) IN1 LIN P4(Y) IN1 LIN P5(X) IN1 LIN P5(Y) IN1 LIN P6(X) IN1 LIN P6(Y) IN1 LIN P7(X) IN1 LIN P7(Y) IN1 LIN P8(X) IN1 LIN P8(Y) IN1 LIN P9(X) IN1 LIN P9(Y) IN1 LIN P10(X) IN1 LIN P10(Y) IN1 LIN P11(X) IN1 LIN P11(Y) IN1 LIN P12(X) IN1 LIN P12(Y) IN1 LIN P13(X) IN1 L
ISDU Index 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 DPP1 Index Name of the Parameter IN1 LIN P14(X) IN1 LIN P14(Y) IN1 LIN P15(X) IN1 LIN P15(Y) IN1 LIN P16(X) IN1 LIN P16(Y) IN1 LIN P17(X) IN1 LIN P17(Y) IN1 LIN P18(X) IN1 LIN P18(Y) IN1 LIN P19(X) IN1 LIN P19(Y) IN1 LIN P20(X) IN1 LIN P20(Y) IN1 LIN P21(X) IN1 LIN P21(Y) IN1 LIN P22(X) IN1 LIN P22(Y) IN1 LIN P23(X) IN1 LIN P23(Y) IN1 LIN P24(X) IN1 LIN P24(Y) IN 1 TOT BASE IN 1 T
ISDU Index DPP1 Index Name of the Parameter 333 334 335 336 337 338 339 340 341 342 343 344 345 IN2 CONFIGURATION IN2 START VALUE IN2 END VALUE IN2 DECIMAL POINT IN2 SCALE UNITS IN2 SAMPLING TIME (ms) IN2 AVERAGE FILTER IN2 OFFSET IN2 LINEARIZATION IN2 TOTALIZATION __ __ __ 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 IN2 LIN P1(X) IN2 LIN P1(Y) IN2 LIN P2(X) IN2 LIN P2(Y) IN2 LIN P3(X) IN2 LIN P3(Y) IN2 LIN P4(X) IN2 LIN P4(Y) IN2 LIN P5(X) IN2 LIN P5(Y) IN2 LIN P6(X) IN2 L
ISDU Index 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 DPP1 Index Name of the Parameter IN2 LIN P10(X) IN2 LIN P10(Y) IN2 LIN P11(X) IN2 LIN P11(Y) IN2 LIN P12(X) IN2 LIN P12(Y) IN2 LIN P13(X) IN2 LIN P13(Y) IN2 LIN P14(X) IN2 LIN P14(Y) IN2 LIN P15(X) IN2 LIN P15(Y) IN2 LIN P16(X) IN2 LIN P16(Y) IN2 LIN P17(X) IN2 LIN P17(Y) IN2 LIN P18(X) IN2 LIN P18(Y) IN2 LIN P19(X) IN2 LIN P19(Y) IN2 LIN P20(X) IN2 LIN P20(Y) IN2 LIN P21(X) IN2 LIN P21(Y) IN
ISDU Index 390 391 392 393 DPP1 Index Name of the Parameter IN2 LIN P23(X) IN2 LIN P23(Y) IN2 LIN P24(X) IN2 LIN P24(Y) 394 395 396 397 398 399 400 IN2 TOT BASE IN2 TOT DIVIDER IN2 TOT DECIMAL POINT IN2 TOT SCALE UNITS __ __ __ 401 402 403 404 405 406 407 408 LINKAGE FACTOR LINKAGE DIVIDER LINKAGE ADDITIVE VALUE LINKAGE DECIMAL POINT LINKAGE SCALE UNITS __ __ __ 409 410 411 412 413 414 415 416 417 418 419 420 421 422 IN1 FACTOR IN1 DIVIDER IN1 ADDITIVE VALUE IN1 DECIMAL POINT IN1 SCALE UNITS IN2 FAC
ISDU Index 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 DPP1 Index Length in bytes PRESELECTION VALUES PRESELECTION 1 R/W 4 PRESELECTION 2 R/W 4 PRESELECTION 3 R/W 4 PRESELECTION 4 R/W 4 __ R/W 4 __ R/W 4 PRESELECTION 1 MENU PRES1 SOURCE 1 R/W 4 PRES1 MODE 1 R/W 4 PRES1 HYSTERESIS 1 R/W 4 PRES1 PULSE TIME 1 (ms) R/W 4 PRES1 OUTPUT TARGET 1 R/W 4 PRES1 OUTPUT POLARITY 1 R/W 4 PRES1 OUTPUT LOCK 1 R
ISDU Index 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 DPP1 Index Length in bytes PRESELECTION 4 MENU PRES4 SOURCE 4 R/W 4 PRES4 MODE 4 R/W 4 PRES4 HYSTERESIS 4 R/W 4 PRES4 PULSE TIME 4 (ms) R/W 4 PRES4 OUTPUT TARGET 4 R/W 4 PRES4 OUTPUT POLARITY 4 R/W 4 PRES4 OUTPUT LOCK 4 R/W 4 PRES4 START UP DELAY 4 R/W 4 PRES4 EVENT COLOR 4 R/W 4 __ R/W 4 __ R/W 4 SERIAL MENU UNIT NUMBER R/W 4 SERIAL BAUD RATE R
ISDU Index 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 DPP1 Index Name of the Parameter START DISPLAY SOURCE SINGLE SOURCE DUAL TOP SOURCE DUAL DOWN LARGE DISPLAY SOURCE LARGE COLOR BRIGHTNESS (%) CONTRAST SCREEN SAVER (s) UP-DATE-TIME (ms) FONT __ __ __ Length in bytes DISPLAY MENU R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 R/W 4 Access Default Value Range 0 0 0 1 0 0 0 80 1 0 100 0 0 0 0 0..5 0..11 0..11 0..11 0…6 0…11 0..2 10..100 0..2 0..
Application specific commands Index Subindex Value TARA INPUT 1 2 0 160 TARA INPUT 2 2 0 161 TARA INPUT 1 + 2 2 0 162 ADD TO TOTAL 1 2 0 163 ADD TO TOTAL 2 2 0 164 RESET TOTAL 1 RESET TOTAL 2 2 2 0 0 165 166 RESET TOTAL LINKAGE 2 0 167 TEACH PRESELECTION 1 2 0 168 TEACH PRESELECTION 2 2 0 169 TEACH PRESELECTION 3 2 0 170 TEACH PRESELECTION 4 2 0 171 SCROLL DISPLAY 2 0 172 SERIAL PRINT 2 0 173 SET TO RED 2 0 174 SET TO GREEN 2 0 175 SET TO YELLOW
LOCK RELEASE 2 0 184 Self-locking of all outputs/relays. (d) IO-Link Prozessdaten Process input (32 bytes) View from the IO-link master! Byte Bit Function Output Status: Ctrl. Out 1 Output Status: Ctrl. Out 2 Output Status: Ctrl. Out 3 Output Status: Ctrl. Out 4 Output Status: Rel. 1 Output Status: Rel.
Process output data (8 Byte) View from the IO-link master! Byte Bit 0…3 0…31 4…7 32…63 Function IO-Link display value 1 (Data type: long - incl. sign) IO-Link display value 2 (Data type: long - incl. sign) Logic - Assignement table of the transferred unit Transferred value (decimal) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Ax350_06a_oi_e.
Error type Error code Name 32768 / 0x 8000 Application errors in the device-no details 32785 / 0x 8011 32786 / 0x 8012 Index does not exist Subindex does not exist 32800 / 0x 8020 Service not available at this time 32803 / 0x 8023 Access denied 32816 / 0x 8030 Parameter value out of range 32817 / 0x 8031 Parameter value greater than specified range 32818 / 0x 8032 Parameter value less than specified range 32819 / 0x 8033 32820 / 0x 8034 32821 / 0x 8035 Parameter length too large Parameter l
Declaration of Conformity IO-Link module Ax350_06a_oi_e.
Display of scale units SCALE UNITS This parameter defines the required engineering unit. This parameter does not affect the calculation of the display value. The number of decimal places must be defined with the parameter DECIMAL POINT. 0 V Default 1 mV 2 A 3 mA 4 km/h 5 mph 6 feet/min 7 inch/min 8 g 9 kg 10 oz 11 W 12 kW 13 VA 14 mm 15 cm 16 m 17 inch 18 feet 19 C 20 F 21 K 22 1/sec 23 1/min 24 1/h 25 gal/min 26 Pa 27 kPa 28 % A customized unit with up to 16 digits can be edited using this parameter.
Parameter / serial codes 6 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Menu # GENERAL MENU GENERAL MENU GENERAL MENU GENERAL MENU GENERAL MENU GENERAL MENU GENERAL MENU GENERAL MENU GENERAL MENU IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 PROPERTIES IN 1 LINEARIZATION IN 1
Continuation „Parameterliste“: # 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 Menu IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION
Continuation „Parameter“: # 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 Menue IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEA
Continuation „Parameter“ # 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 Menue IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES IO LINK PROPERTI
Continuation „Parameter“ # 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 Menue PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 3 MENU PRESELECTION 3 MENU PRESELECTION 3 MENU PRESELECTION 3 MENU PRESELECTI
Continuation „Parameter“ # 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 Menue ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPL
Serial codes of commands: Serial Code 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 Ax350_06a_oi_e.
Linearization The linearization function of this unit allows converting a linear input signal into a non-linear developing (or vice versa). There are 24 programmable x/y coordinates available for input 1 and input 2, which can be set in any desired distance over the full conversion range. Between two coordinates, the unit uses linear interpolation. Therefore it is advisable to use more coordinates in a range with strong curves and only a few coordinates where the curvature is less.
Application Example: We like to display the filling quantity (volume) of a tank as shown below, with use of a pressure sensor mounted to the bottom of the tank. With this application the analogue pressure signal is proportional to the filling level, but not to the filling quantity. Volume P16_x P16_y P15_x P15_y P10_x P16_x Pressure P15_x 0-20 mA P07_y P01_y P10_x P01_x P10_y P01_x Pressure Sensor To solve the problem, we divide the non-linear part of the tank into 14 parts.
Dimensions Dimension in mm [inch] Ax350_06a_oi_e.
Technical specifications 6 7 Technical Specifications: Connections: Power supply (DC): Power supply (AC): (Option AC) Encoder supply: Reference output: Analog inputs: Control inputs: Analog output: (Option AO/AR) Control outputs: (Option AO/AR/CO/CR) Relay outputs: (Option RL) Serial interface: (Option AO/AR/CO/CR) IO-Link: (Option IO) Connector type: Input voltage: Protection circuit: Consumption: Fuse protection: Input voltage: Power consumption: Fuse protection: DC version: Output current: AC v
Continuation “Technical specifications” Display: Housing: Ambient temperature: Conformity and standards: Type: Display range: Digit height: Color: Operation: Material: Mounting: Dimensions (w x h x d): Cut out (w x h): Protection class: Weight: Operation: Storage: EMC 2014/30/EU: LV 2014/35/EU: (Only for option AC and RL) RoHS (Ⅱ) 2011/65/EU RoHS (Ⅲ) 2015/863: Ax350_06a_oi_e.