Technical data
Cabling
5-21
5
2. Guide the free end of a DC power cable, with about
1
/2 inch of
insulation stripped from the wires, to the terminal block
supplied with the DC system. Clamp the DC leads (positive,
negative, and ground) to the terminal block.
!
Caution
The connection to DC power consists of three wire leads
(no larger than #12 AWG, fine strand or solid, but
capable of handling at least 10 Amps of current). To
avoid grounds or shorts, exercise care when securing
the wires to the connector.
Note For additional protection if the conditions of the site
call for it, you may wish to also use the chassis ground
point on the rear wall of the unit (the GND connection
with a
1
/4 x 20 thread located in the lower right corner
of the back panel, as viewed from the rear). This
ground point is to be connected to the equipment rack
or other reliable path to ground.
.
3. Assemble the clam-shell connector housing around the wires
as shown in the diagram above. Secure a length of Tyrap
around the housing to reinforce the assembly.
GROUND
11302.00 9503
−24/−48VDC
+24/+48VDC