Projector User Manual

GT10/GT30 4.4 Connecting the FP2/FP2SH
49
4.4 Connecting the FP2/FP2SH
4.4.1 Connecting to the COM. Port
AIP81842D
GT30
FP2/FP2SH CPU COM. port
GT10
FP2/FP2SH communication format settings
System register no. Item Value Set
412 Selection of target use of RS232C port Computer link
413
Data length 8 bits
Parity check Yes
Parity setting Odd
Stop bits 1 bit
Line return code CR
Start code No STX
414 Baud rate setting 19200 bits/s
415 Unit number 1
416 Modem connection No connection
PLC communication cable: D–sub 9–pin loose–wire cable (AIP81842D)
1
2
3
4
5
6
7
8
9
Signals on D–sub side
Pin no. Wire color GT COM port
1–
2 White RD
3 Green SD
4–
5–
6–
7 Brown GND
8–
9–
Specifications Length Product no.
D–sub 9–pin
Single–side
loose wiring
AIP81842D
2m
5mm
35mm
2000mm
Wires’ cross section: 0.25mm
2
Connecting to the FP2/FP2SH COM. port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6 N.C.
7
8
9
N.C.
ER
SD SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10/GT30
Pin no. on PLC side
No. 3 (green)
No. 2 (white)
No. 7 (brown)
PLC side GT main unit side
Pin no.Pin no.
Abbreviation
Abbreviation