Microcontroller User's Manual

30-6 MCF5282 User’s Manual MOTOROLA
Memory Map and Registers
30.5.3.2 Reset Configuration Register (RCON)
At reset, RCON determines the default operation of certain chip functions. All default
functions defined by the RCON values can only be overridden during reset configuration
(see Section 30.6.1, “Reset Configuration”) if the external RCON
pin is asserted. RCON is
a read-only register.
3 BME Bus monitor enable. This read/write bit enables the bus monitor to operate during external bus cycles.
0 Bus monitor disabled for external bus cycles.
1 Bus monitor enabled for external bus cycles.
Table 30-2 shows the read/write accessibility of this write-once bit.
2–0 BMT Bus monitor timing. This field selects the timeout period (in system clocks) for the bus monitor.
000 65536
001 32768
010 16384
011 8192
100 4096
101 2048
110 1024
111 512
Table 30-2 shows the read/write accessibility of this write-once bit.
15 10 9 8 7 6 5 4 3 2 1 0
Field RCSC RPLLSEL RPLLREF RLOAD BOOTPS BOOTSEL MODE
Reset 0000_0000_1110_0000
R/W R
Address IPSBAR + 0x11_0008
Figure 30-3. Reset Configuration Register (RCON)
Table 30-5. RCON Field Descriptions
Bits Name Description
15–10 Reserved, should be cleared.
9–8 RCSC Chip select configuration. Reflects the default chip select configuration. The default function of the
chip select configuration can be overridden during reset configuration. See Table 30-6 for bit
encodings.
7 RPLLSEL PLL mode select. Reflects the default PLL mode.
0 1:1 PLL mode
1 Normal PLL mode (This is the value used for the MCF5282.)
The default PLL mode can be overridden during reset configuration. If the default is overridden, the
clock module’s SYNSR[PLLSEL] bit reflects the PLL mode.
Table 30-4. CCR Field Descriptions (continued)
Bits Name Description