User's Manual
Table Of Contents
- DISTRIBUTED I/O SYSTEM
- CONTENTS
- INTRODUCTION
- INSTALLATION
- THE DIOS PIU AND PICCOLO-XR UNITS
- APPENDIX A: PIU and PICCOLO-XR SPECIFICATIONS
- APPENDIX B: MODELS and ACCESSORIES
- APPENDIX C: ANTENNA
- APPENDIX D: PIU/PICCOLO–XR MOUNTING TEMPLATES
APPENDIX A: PIU AND PICCOLO-XR SPECIFICATIONS
40
PIU Mode
(Using a 12 V or 6 V external power source)
Radio Transmission
(TX power-10 mW) 25 – 40 mA (PWR IN =14 V)
65 – 90 mA (PWR IN = 6 V)
(TX power-100 mW) 30 – 65 mA (PWR IN =14 V)
85 – 135 mA (PWR IN = 6 V)
Standby current
Radio Receives
13 – 18 mA (PWR IN =14 V)
30 – 38 mA (PWR IN = 6 V)
Sleep Mode
LPM0
200 – 320 μA (See Note 2 on p.
41.)
LPM3 130 – 250 μA (See Note 2 on p.
41.)
Power Monitors
Power OK Voltage (Service Toolkit Adjustable Default
= 12 V DC) 200 mV
LOW Power Voltage
(Service Toolkit Adjustable Default
= 11.2 V DC) 200 mV
Very Low Battery
(Service Toolkit Adjustable Default
= 10.8 V DC) 200 mV
Reverse Input Voltage
Connection
Protected