Users Manual Part 1

4.4
Cabinet Installation
Depending on the MTS type, installing the MTS cabinet within a site may include wall fixing or floor
fixing.
IMPORTANT:
To enable service access and assure the passive cooling ventilation, the free space above the
cabinet must be 20 cm at minimum The antenna cabling may require additional space.
Allow at least 80 cm of floor space in front of the cabinet to permit access during installation.
Although all maintenance, expansion, cabling, and antenna connections can be performed from
the front or top. The required space towards the wall is ensured by an integrated spacer on the
back of the cabinet.
Secure the cabinet to the floor for optimum stability.
4.4.1
Cabinet Bracing Considerations
The MTS cabinet is self-supporting. In seismically active areas, additional bracing of the cabinet could
be required. However, the bracing hardware must be locally procured.
NOTICE: There are no specific procedures within this manual for bracing cabinets in active
seismic areas.
4.4.2
Floor Mounting Instructions
The MTS LiTE, MTS 2, MTS 4, and Expansion Cabinets can be mounted directly to the floor using the
mounting brackets, see Figure 17: MTS – Mounting Brackets on page 95.
NOTICE: The floor mounting brackets are not part of standard MTS shipment. If floor mounting
brackets are to be used, they must be ordered as an accessory.
Partnumber 01015026001 STANDARD FLOOR MOUNT SET MTS
6802800U74-AP
Chapter 4: Hardware Installation
94