Users Manual Part 1

MTS 800 MHz/
900 MHz Config-
uration
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W) Comment
MTS4 with 4 BRs
w. MTCC/ATCC
144
5
1345 2205 1515 141
0
1310 High power PA,
fans
NOTICE:
All the values in the table are calculated from AC = 230 V
Add additional 5% for 110 V
Charging is up to 6 A per PSU
3.7.2.1.6
Power Loads and Heat Dissipation – Expansion Cabinet 800 MHz
Table 18: Typical Power Loads and Heat Dissipation Values – Expansion Cabinet 800 MHz
Configuration
Expansion Cabi-
net Consump-
tions MTS 800
MHz Configura-
tion
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W)
Comment
TETRA TX 10 W
MTS4 with 1 BR
w. MTCC/ATCC
320 310 705 370 235 225 High power PA,
fans
MTS4 with 2 BRs
w. MTCC/ATCC
530 510 915 570 365 345 High power PA,
fans
MTS4 with 3 BRs
w. MTCC/ATCC
855 825 1620 940 605 575 High power PA,
fans
MTS4 with 4 BRs
w. MTCC/ATCC
108
0
1040 1840 1155 745 705 High power PA,
fans
TETRA TX 25 W and TEDS TX 10 W
MTS4 with 1 BR
w. MTCC/ATCC
405 380 790 455 395 370 High power PA,
fans
MTS4 with 2 BRs
w. MTCC/ATCC
700 650 1085 740 685 635 High power PA,
fans
MTS4 with 3 BRs
w. MTCC/ATCC
113
0
1055 1890 1215 110
5
1030 High power PA,
fans
MTS4 with 4 BRs
w. MTCC/ATCC
144
5
1345 2205 1515 141
0
1310 High power PA,
fans
NOTICE:
All the values in the table are calculated from AC = 230 V
Add additional 5% for 110 V
Charging is up to 6 A per PSU
6802800U74-AP
Chapter
3: Site Preparation
86