Users Manual Part 1

MTS 260 MHz
Configuration
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W) Comment
MTS2 with 2 BRs 430 380 810 470 420 370 Two TX ant.,
low power PA
NOTICE:
All the values in the table are calculated from AC = 230 V
Add additional 5% for 110 V
Charging is up to 6 A per PSU
3.7.2.1.4
Power Loads and Heat Dissipation – Expansion Cabinet 260 MHz
Table 16: Typical Power Loads and Heat Dissipation Values – Expansion Cabinet 260 MHz
Configuration
Expansion Cabi-
net Consump-
tions MTS 260
MHz Configura-
tion
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W)
Comment
TETRA TX 10 W
MTS4 Exp. Cab.
w 1 BR w. ATCC
240 230 625 290 235 225 Low power PA,
fans
MTS4 Exp. Cab.
w. 2 BRs w.
ATCC
375 355 755 410 365 345 Low power PA,
fans
MTS4 Exp. Cab.
w. 3 BRs w.
ATCC
620 590 1380 705 605 575 Low power PA,
fans
MTS4 Exp. Cab.
w. 4 BRs w.
ATCC
760 720 2005 835 745 705 Low power PA,
fans
NOTICE:
All the values in the table are calculated from AC = 230 V
Add additional 5% for 110 V
Charging is up to 6 A per PSU
6802800U74-AP
Chapter
3: Site Preparation
84