Users Manual Part 1

Expansion Cabi-
net 800 MHz
Configuration
AC
(W)
Heat
AC
(W)
AC
When
Charg-
ing (W)
Heat AC
When
Charging
DC-48
V (W)
Heat
DC (W)
Com-
ment
MTS4 Exp. Cab.
w. 2 BRs w.
MTCC/ATCC
640 590 1020 650 625 575 Fans
MTS4 Exp. Cab.
w. 3 BRs w.
MTCC/ATCC
1040 965 1800 1080 1015 940 Fans
MTS4 Exp. Cab.
w. 4 BRs w.
MTCC/ATCC
1320 1220 2085 1335 1290 1190 Fans
3.7.2.1.3
Power Loads and Heat Dissipation – MTS 260 MHz
Table 15: Typical Power Loads and Heat Dissipation Values – MTS 260 MHz Configurations
MTS 260 MHz
Configuration
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W) Comment
TETRA TX 10 W
MTS2 with 1 BR 140 130 520 185 135 125 No combining,
low power PA,
no fans
MTS2 with 1 BR
w. Hybrid
165 155 545 210 160 150 Low power PA,
no fans
MTS2 with 2 BRs 245 225 625 280 240 220 Two TX ant.,
low power PA,
no fans
MTS2 with 2 BRs
w. Hybrid
295 275 675 330 285 265 Low power PA,
no fans
MTS4 with 1 BR
w. ATCC
240 230 625 290 235 225 Low power PA,
fans
MTS4 with 2 BRs
w. ATCC
375 355 755 410 365 345 Low power PA,
fans
MTS4 with 3 BRs
w. ATCC
620 590 1380 705 605 575 Low power PA,
fans
MTS4 with 4 BRs
w. ATCC
760 720 2005 835 745 705 Low power PA,
fans
TETRA TX 25 W
MTS2 with 1 BR 230 205 610 280 225 200 No combining,
low power PA
6802800U74-AP
Chapter 3: Site Preparation
83