Users Manual Part 1
Expansion Cabi-
net Consump-
tions MTS 400
MHz Configura-
tion
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W) Comment
MTS4 Exp. Cab.
w. 1 BR w.
MTCC/ATCC
375 350 755 410 365 340 Fans
MTS4 Exp. Cab.
w. 2 BRs w.
MTCC/ATCC
640 590 1020 645 625 575 Fans
MTS4 Exp. Cab.
w. 3 BRs w.
MTCC/ATCC
103
5
960 1800 1075 101
0
935 Fans
MTS4 Exp. Cab.
w. 4 BRs w.
MTCC/ATCC
132
0
1220 2080 1330 129
0
1190 Fans
NOTICE:
• All the values in the table are calculated from AC = 230 V
• Add additional 5% for 110 V
• Charging is up to 6 A per PSU
Table 14: Typical Power Loads and Heat Dissipation Values – Expansion Cabinet 800 MHz BR-Arch-2
Configuration
Expansion Cabi-
net 800 MHz
Configuration
AC
(W)
Heat
AC
(W)
AC
When
Charg-
ing (W)
Heat AC
When
Charging
DC-48
V (W)
Heat
DC (W)
Com-
ment
TETRA TX 10 W
MTS4 Exp. Cab.
w 1 BR w. MTCC/
ATCC
255
245 635 300 250 240 Fans
MTS4 Exp. Cab.
w. 2 BRs w.
MTCC/ATCC
400 380 780 435 390 370 Fans
MTS4 Exp. Cab.
w. 3 BRs w.
MTCC/ATCC
655 625 1420 740 640 610 Fans
MTS4 Exp. Cab.
w. 4 BRs w.
MTCC/ATCC
810 770 2055 885 795 755 Fans
TETRA TX 25 W
MTS4 Exp. Cab.
w. 1 BR w.
MTCC/ATCC
375 350 755 410 370 345 Fans
6802800U74-AP
Chapter 3: Site Preparation