Users Manual Part 1
MTS 400 MHz
Configuration
AC
(W)
Heat
AC
(W)
AC
When
Charg
ing
(W)
Heat AC
When
Charg-
ing (W)
DC
-48
V
(W)
Heat
DC
(W) Comment
MTS2 with 2 BRs
w. Hybrid
295 275 675 330 285 265 Low power PA,
no fans
MTS4 with 1 BR
w. MTCC/ATCC
240 230 625 290 235 225 Low power PA,
fans
MTS4 with 2 BRs
w. MTCC/ATCC
375 355 755 410 365 345 Low power PA,
fans
MTS4 with 3 BRs
w. MTCC/ATCC
620 590 1380 705 605 575 Low power PA,
fans
MTS4 with 4 BRs
w. MTCC/ATCC
760 720 2005 835 745 705 Low power PA,
fans
TETRA TX 25 W / 40 W and TEDS TX 10 W
MTS LiTE and
MTS2 with 1 BR
230 205 610 280 225 200 No combining,
low power PA
(25W)
MTS LiTE and
MTS2 with 1 BR
370 345 750 420 365 340 No combining,
high power PA
(40W)
MTS2 with 1 BR
w. Hybrid
230 205 610 280 225 200 Low power PA
(10W)
MTS2 with 1 BR
w. Hybrid
370 345 750 420 365 340 High power PA,
fans (25W)
MTS2 with 2 BRs 430 380 810 470 420 370 Two TX ant.,
low power PA
(25W)
MTS2 with 2 BRs 630 580 1010 670 615 565 Two TX ant.,
high power PA
(40W)
MTS2 with 2 BRs
w. Hybrid
430 380 810 470 420 370 Low power PA
(10W)
MTS2 with 2 BRs
w. Hybrid
630 580 1010 670 615 565 High power PA,
fans (25W)
MTS4 with 1 BR
w. MTCC/ATCC
370 345 750 420 365 340 High power PA,
fans
MTS4 with 2 BRs
w. MTCC/ATCC
630 580 1010 670 615 565 High power PA,
fans
MTS4 with 3 BRs
w. MTCC/ATCC
102
5
950 1785 1110 100
0
925 High power PA,
fans
6802800U74-AP
Chapter 3: Site Preparation
77