Users Manual Part 1

Air Quality Considerations
For cabinet-mounted equipment operating in an area without environmental control, the airborne
particulates level must not exceed concentration defined in ETSI norm EN300 019 1-3 Class 3.
Salt mist like sea salt and road salt is excluded and shall always be avoided.
3.7
Electrical Requirements
WARNING: The DC power source providing power to the MTS must be compliant with
requirements specified for a safety extra low voltage circuit (SELV) per EN60950.
WARNING: Any device (that is power supply) providing isolation between the AC mains and the
MTS must provide reinforced insulation to hazardous voltages.
CAUTION: All electrical wiring for the MTS site must meet the requirements of all applicable
local codes and regulations.
CAUTION: The battery installation needs a short circuit protection closest to the batteries.
Install the batteries in the same building and provide proper ventilation.
3.7.1
Applicable Codes and Practices
IMPORTANT: If other codes and practices are beneficial, see your local standards.
Adhere to the following list of selected codes and practices:
Motorola Standards and Guidelines for Communications Sites, R56 manual
UK - RPSG Installation Manual, System Quality Standard, specification number 2200 and part
number. 68P02200F01.
UK - Institution of Engineering and Technology (IET) - BS 7671:2001 16th Edition Wiring
Regulations (Appendix 12, Cable Capacities of Conduit and Trunking).
UK - Antenna System Installation Practice, issued by The Directorate of Telecommunications of the
UK Home Office.
UK - Details of Earthing Requirements for Masts, Aerial Feeder Cables, and Radio Equipment
Rooms, issued by The Directorate of Telecommunications of the UK Home Office.
GERMANY - VDE0100 Errichten von Starkstromanlagen bis 1000 Volt.
GERMANY - VDE0185 Blitzschutzanlagen.
GERMANY - VDE0510 Akkumulatoren und Batterieanlagen.
GERMANY - VDE0855 Antennenanlagen, Errichtung und Betrieb.
3.7.2
AC and DC Power Supplies
The MTS cabinet is equipped with a high efficiency switch mode Power Supply Unit (PSU).
Operating modes are as follows:
DC only operation (within -41 VDC to -60 VDC)
AC only operation (within 90 VAC to 264 VAC; 45 Hz to 66 Hz)
6802800U74-AP
Chapter 3: Site Preparation