The equipment cabinet may be installed against adjacent equipment, however the following minimal
distances must be retained:
25 mm on both sides of the cabinet
800 mm of free space in front of the cabinet
The cabinet front door has hinges on both sides and it can be opened right, left, or removed. Figure 11:
Suggested MTS 4 Site Layout
on page 70 shows the cabinet layout within a suggested site.
Additional free space is recommended at the front of the cabinet to allow service personnel easy
access to the equipment.
CAUTION: To enable service access and assure the passive cooling ventilation, the free space
above the cabinet must be at least 20 cm. The antenna cabling may require additional space.
NOTICE: Enable the opening of all doors to the equipment room to at least 90 degree. The
cabinet has a removable door.
Figure 11: Suggested MTS 4 Site Layout
Service Area
rack rackMTS4
minimum 25mm
minimum
900mm
minimum
800mm
570mm
HVACHVAC
3.2.4
Expansion Cabinet Considerations
The Expansion Cabinet dimensions are: 550 mm (width)/570 mm (depth)/1430 mm (height) as shown
in the following figure.
6802800U74-AP
Chapter 3: Site Preparation
70