Users Manual Part 1

Figure 51: MTS LVD Kit Relay Connection Diagram – Dual PSU, Single Battery
A To PSU 1
1 Connect to Power 1 on Site Controller 1
2 To DC Main circuit breaker
B To PSU 2
3 To DC Main circuit breaker
4 Connect to Power 2 on Site Controller 1 or
Power 1 on Site Controller 2
5 Power Supply 48 VDC
A
LVD G9EA LVD G9EA
-E1.1 -E1.2
-E1.3
-E1.4
B
1
2 3
4
5
The number of LVD Kits used depends on the type of MTS:
For MTS 2, only one LVD is necessary.
For MTS 4 with two batteries, two LVD devices have to be used (one LVD for each PSU).
For MTS 4 powered with a single battery, LVD battery cables should be connected in parallel. LVD
controller cables should be connected to separate PSUs so each PSU controls a LVD.
For MTS with XHUB configuration, see the first two points in this list.
4.5.3.8
Installing the MTS LVD Kit
Procedure:
1 Unpack the kit and check if all items are present.
WARNING: Working on live system is hazardous, switch off power!
2 Perform the following actions:
a Connect the battery cables (Ø6 ring terminals apply) using a PH2 screwdriver.
Recommended torque is max 2 Nm.
6802800U74-AP
Chapter 4: Hardware Installation
122