Chapter 3: Site Preparation
Service Area
rack MTS2 rack
CAUTION: To enable service access and assure the passive cooling ventilation, the free space
above the cabinet must be at least 20 cm. The antenna cabling may require additional space.
NOTICE: Enable the opening of all doors to the equipment room to at least 90 degree. The
cabinet has a removable door.
Figure 8: Suggested MTS 2 Site Layout
minimum 45mm.
3.2.3
MTS 4 Cabinet Considerations
The equipment cabinet dimensions are: 550 mm (width)/570 mm (depth)/1430 mm (height) as shown
in the following figure.
HVAC
HVAC
minimum
800m.
472mm.
minimum
600m.