Product Manual

Display Parameter [Default]
[P.0] Remote Start Delay Timing (Input #7) [ 1"]
Range: 1-59 secs or 1-15 mins
Seconds or minutes of continuous REMOTE START command to initiate the auto-
matic engine start (see section 7.0 and [P20] in this section).
[P.1] Remote Stop Delay Timing (Input #7) [ 1"]
Range: 1-59 secs or 1-15 mins
Seconds or minutes of continuous absence of the REMOTE START command to
initiate the stop cycle (see section 7.0 and [P.20] in this section).
[P.2] Crank Timing (Output #10) [ 5"]
Range:1-20 seconds Maximum insertion time of the Starter Motor.
[P.3] Engine Running Trigger (Input #1) [ 8.0]
Range: 3V-24V, [inh]. If the voltage of the Charger Alternator rises above the [set-
ting], the Starter Motor is disconnected.
[P.4] Rest Timing [ 3"]
Range: 3-20 secs. Time interval between starting attempts
[P. 5] Starting Attempts [ 3 ]
Range: 1-10 This parameter sets the number of attempts in the automatic start cycle
[P.6] Generator UnderVoltage, short-circuit [ inh.]
Range: 80-400V. If the voltage drops under the [setting] for at least 6 secs, or under
[setting]-20% for 1 sec, the Under-Voltage protection [Lo U] will shut down the engine.
[P.7] Generator Over-Voltage [500V]
Range: 110-550V or [inh.]. If the Generator voltage rises above the [setting] for at
least 2 seconds, the EP6 will energize the over voltage protection [Hi U] (see section
4.0) to stop the engine. The [inh.] code inhibits the over voltage.
[P.8] Generator Under-Frequency [Inh.]
[inh.] 1 to 99Hz ([inh]=disables the under frequency)
This protection is delayed by about 6 seconds. The EP6 shuts down the engine and
the display will show the [Lo H] message.
[P.9] Generator Over-Frequency [55]
45 Hz to [inh.] ([inh.] disables the over frequency)
This protection is delayed by about 2 seconds. The EP6 shuts down the engine and
displays [Hi H]
[P.10] Current Transformer Size [...]
The range is 10/5 up to 1000/5
[P.11] Generator Overload Setting [inh.]
Range: [inh.] to 1000 AThe EP6 shuts down the engine after a delay of 6 secs and
shows the message [E05].
[P.12] Generator Failure Alarm [OFF]
selection: [on] or [OFF].The code [on] enables the Generator failure alarm. The EP6
shows the [E04] message and the engine will shut down.
[P.13] Glow Plugs/Choke Control (Output #11) [ 5"]
Range: 1 to 99 secs.The EP6 energizes the output #11 for the programmed time.
[P.14] Output Control [ 0 ]
The following options are available:
[ 0] None - [ 1] Choke Control - [ 2] Glow Plugs Control - [ 3] Choke Control
[P.15] Belt Break Control [ON]
Selection: [on] or [OFF]. The Belt Break alarm is indicated by means of the message
[bELt]
[P.16]
Stop Solenoid Timing [ 2"]
Range: 2-99 secs. Duration of the Stop cycle.
PROTECTIONS EP6 ENGINE PROTECTION
M
39.12.
2
REV.0-10/05
12/10/05 M39GB