User Manual

MADE IN ITALY
language
SYNCHRONOUS, THREE-PHASE, SELF-EXCITED, SELF-REGULATED, BRUSHLESS (WITHOUT AVR)
SYNCHRONOUS, THREE-PHASE, SELF-EXCITED, SELF-REGULATED (WITH AVR)
WITHOUT AVR WITH AVR
Continuos power 10 kVA
Stand-by power 11 kVA
Three phase voltage 230/115 Vac
Frequency 50 Hz
Cos j 1
Model A.V.R. / HVR 11E
Voltage regulation acc. ± 5 % ± 1 %
Sustained short circuit current ≤ 2.5 In
Transient dip (100% load) < 15 %
Recovery time /
Eciency at 100% load
79.5 % (230V - Cos j 1)
80 % (230V - Cos j 1)
Insulation Class H
Connection - Terminals Series - N°4
Electromagnetic compatibility (
R.F.I. suppr.)
EN55011
Waveform distorsion - THD <5% <5.5%
Thelephone interference - THF /
altErnator
REACTANCES (10 kVA - 230/115V)
Direct axis synchronuos - Xd /
Direct axis transient - X’d /
Subdirect axis transient - X”d /
Quadrature axis synchronuos - Xq /
Quadr. axis subtransient - X”q /
Negative sequence - X2 /
Zero sequence - X0 /
TIME CONSTANTS
Transient - T’d /
Subtransient - T”d /
Open circuit - T’do /
Armature - Ta /
Short-circuit ratio Kcc /
IP protection degree IP 23
Cooling air flow 0.082 m³/sec.
Coupling | Bearing Direct SAE 5 -7 ½ - N°1
GE SX-10000 KTDM
Start and stop engine key
Low oil pressure warning light with shutdown
High cooling temperature warning light with shutdown
Battery charge warning light fault
Low fuel warning light
Glow plug light
Digital multifunction meter : Voltmeter - Frequencymeter - Total Hoursme-
ter - Partial Hoursmeter (resettable) - Battery voltage
Fuel level gauge
Emergency stop buttom
Circuit breaker
ELCB-GFI (Ground Fault Interruptor)
Circuit breaker for 230V 16A socket
Output sockets: 1x230V 32A 2P+T CEE
1x230V 16A 2P+T CEE
1x230V 16A 2P+T Schuko
Earth terminal (PE)
Start and stop engine key
Low oil pressure warning light with shutdown
High cooling temperature warning light with shutdown
Battery charge warning light fault
Low fuel warning light
Glow plug light
Digital multifunction meter : Voltmeter - Frequencymeter - Total Hoursme-
ter - Partial Hoursmeter (resettable) - Battery voltage
Fuel level gauge
Emergency stop buttom
Circuit breaker
ELCB-GFI (Ground Fault Interruptor)
230/115V CTE Voltage switch
Thermal switches for single sockets protection
Output sockets: 1x230V 32A 2P+T CEE
1x230V 16A 2P+T CEE
2x115V 32A 2P+T CEE
1x115V 16A 2P+T CEE
Earth terminal (PE)
230V
230/115V (CtE)
manual Control PanEls
Pag 2
01/2017
gEnEral sPECifiCations
Fuel tank capacity 38 lt.
Running time (75% to PRP) 14.5 h
Starter battery 12 Vdc -38Ah
IP protection degree IP 23
* Acoustic power according to European Directive 2000/14/CE
* Measured acoustic power LwA
(pressure LpA)
93 dB(A) (68 dB(A) @ 7m)
* Guaranteed acoustic power LwA
(pressure LpA)
93 dB(A) (68 dB(A) @ 7m)
Performance class (ISO 8528) G2