SYNCHRONOUS, THREE-PHASE, SELF-EXCITED, SELF-REGULATED
WITHOUT AVR WITH AVR
Continuos power 7 kVA
Stand-by power 7.7 kVA
Three phase voltage 400 Vac
Frequency 50 Hz
Cos j 0.8
Model A.V.R. / HVR10
Voltage regulation acc. ± 4 % ± 1.6 %
Sustained short circuit current 3 In
Transient dip (100% load) < 15 %
Recovery time /
Eciency at 100% load
80.5% (400V - Cosj 0.8)
82.5 % (400V - Cos j 0.8)
Insulation Class H
Connection - Terminals Series - N°6
Electromagnetic compatibility
( R.F.I. suppr.)
EN55011
Waveform distorsion - THD < 4 %
Thelephone interference - THF /
altErnator
gEnEral SpEcificationS
Fuel tank capacity 20 lt.
Running time (75% to PRP) 20 h
Starter battery 12 Vdc -18Ah (AE)
IP protection degree IP 23
REACTANCES (7 KVA - 400 V)
REACTANCES AVR (7 KVA - 400 V)
WITHOUT AVR WITH AVR
Direct axis synchronuos - Xd 270 % 222 %
Direct axis transient - X’d 20 % 15 %
Subdirect axis transient - X”d 6.5 % 4.7 %
Quadrature axis synchronuos - Xq 150 % 128 %
Quadr. axis subtransient - X”q / /
Negative sequence - X2 / /
Zero sequence - X0 / /
TIME CONSTANTS
Transient - T’d 33 ms 33 ms
Subtransient - T”d 5.5 ms 6 ms
Open circuit - T’do 450ms 500 ms
Armature - Ta / /
Short-circuit ratio Kcc 0.60 0.72
Grado di Protezione IP IP 23
Cooling air flow 0.062/ m³/sec 0.060/ m³/sec
Coupling | Bearing Direct J609b - N°1
GE S-6500 YDT
Acoustic power LwA
(pressure LpA)
99 dB(A) (74 dB(A) @ 7m)
Performance class (ISO 8528) G2
• Start and stop engine key (AE)
• Low oil pressure shutdown light (AE)
• Battery charge warning light fault (AE)
• Local-Remote Start switch (AE)
• EAS plug (AE)
• Digital multifunction meter: Voltmeter - Frequencymeter -Total Hoursmeter
- Partial Hoursmeter (resettable)
• Fuel gouge
• Fuel valve
• Circuit breaker
• Output sockets: 1x 400V 16A 3P+N+T CEE
1x 230V 16A 2P+T CEE
1x 230V 16A 2P+T Schuko
• Earth terminal (PE)
control panEl