User Manual

MADE IN ITALY
language
GENERATING SET
GE S-6000 YDM
The images are for reference
POWER RATINGS
*
Stand-By single-phase power (LTP)
5.7 kVA (5.1 kW) / 230V /24.8A
* PRP single-phase power 5 kVA (4.5 kW)/ 230 V / 21.7A
* COP single-phase power /
Frequency 50 Hz
Cos j 0.8
4 STROKE OHV, NATURAL ASPIRATED
Model YANMAR L100N
* Stand-By net power 6.5 kWm (8.8 hp)
* PRP net power 5.7 kWm (7.7 hp)
* COP net power /
Cylinders / Displacement 1 / 435 cm³
Bore / Stroke 86 / 75 (mm)
Compression ratio 20 : 1
BMEP (Brake Mean Eective
Pressure : LTP - PRP)
/
Speed governor type Mechanical
FUEL CONSUMPTION
110 % (Stand-by power) 1.5 lt./h
100 % to PRP 1.3 lt./h
75 % to PRP 1 lt./h
50 % to PRP 0.8 lt./h
COOLING SYSTEM Air
Total system cap. - only engine /
Fan air flow /
LUBRICATION SYSTEM
Total oil system capacity /
Oil capacity in sump 1.6 lt.
Oil consumption at full load /
EnginE 3000 rpm
EXHAUST SYSTEM
Maximum exhaust gas flow /
Max. exhaust gas temp. /
Maximum back pressure 4.3 kPa
External diameter exhaust pipe /
ELECTRICAL SYSTEM 12 Vdc (AE)
Starter motor power 0.8 kW
Battery charging alternator cap. 15 A
Cold start 0°C
With cold start aid /
AIR FILTER Dry
Combustion air flow /
HEAT REJECTED AT FULL LOAD
To exhaust system /
To water and oil /
Radiated to room /
To charge cooler /
* Output powers according to ISO 8528-1
air cooled diesel
manual recoil
* Output powers according to ISO 3046-1
DEFINITION
Valid declared powers up to the followings environmental conditions: temperature
25°C, altitude 100 meters above sea level)
LTP power: stand-by power: Maximum available power for use with variable loads for a
yearly number of hours limited at 500 h. No overload is admitted.
PRP power: continue power with variable loads. Maximum power for use with variable
loads for a yearly illimited nubers of hours.
COP power: continuous power with constant load. Maximum power for use with constant
loads for a yearly unlimited numbers of hours.
single-phase
power
FEATURES
Manual recoil (AA)
Low oil pressure automatic engine shut down (AE)
Sockets: 1x 230V 32A 2P+T CEE
1x 230V 16A 2P+T CEE
1x 230V 16A 2P+T Schuko
Circuit breaker
Fuel level gauge
Protective frame and partially covered
Ready for connection to automatic transfer unit EAS (AE)
Meets EC directives for the safety
AVR version on request
Electric Starter on request (AE)