User Manual

Set-up for operation Water cooled systems
M
20.1
REV.2-04/15
12/06/03 M20-R-HO2-GB

Remove the tap and pour the liquid coolant into the
radiator; the quantity and composition of the liquid
coolant are indicated in the motor operating manual.
Replace the tap, ensuring it is perfectly closed.
After relling operations, allow the motor to run for
a brief time and check the level, as it may have di-
minished due to air bubbles present in the cooling
circuit; restore the level with water.
To replace the liquid coolant, follow the operations
described in the motor operating manual.
:
The engine cooling system is originally lled with
coolant type:

During the engine life it is strongly recommended
to use the same coolant type. This is because a
coolant change would require a careful cleaning of
the cooling system, which is not an easy job. A lack
in tacking these precautions would result in the mix
of different additives used in different coolants which
would originate gelatinous substances capable of
obstructing the cooling system.


Do not remove the radiator tap with the motor in
operation or still hot, as the liquid coolant may
spurt out and cause serious burns. Remove the
tap very carefully.

A qualied electrician should carry out electrical con-
nections according to the norms in force.
!

The electrical connection to the User system is a very
important operation: safety and good operation of the
genset and User system depend on a correct electrical
connection.
Before supplying User system always check:
that wires connecting gen-set to the user plant are
suitable to the supplied voltage and are in accordan-
ce to the applicable rules;
wire type, section and length have been calculated
considering environment conditions and in force
norms;
ground is functioning correctly: earth fault relay devi-
ce works only if this connection is operating;
that direction of the phases corresponds to the user
plant phase rotation, and none of the phases has
been accidentally connected to neutral.
The grounding connection to an earthed installation
 for all models equipped with a diffe-
rential switch (circuit breaker). In these groups the
generator star point is generally connected to the
machine’s earthing; by employing the TN or TT di-
stribution system, the differential switch guarantees
protection against indirect contacts.
In the case of powering complex installations re-
quiring or employing additional electrical protection
devices, the coordination between the protection
devices must be veried.
For the grounding connection, use the terminal (12);
comply to local and/or current regulations in force
for electrical installations and safety.