Product Card
Table Of Contents

MADE IN ITALY
Pag 4
language
GENERATING SET
GE 50 PS SX
FEATURES
• Automatic voltage regulation “AVR” with three-phase sensing
• Round edges for a better rain flow
• Bunded base suitable to contain any liquids leakage from engine avoiding
environmental pollution
• External caps for oil and water drain
• Large doors for better and easy maintenance (air, oil, fuel filters replacement)
• Central lifting eye
• Forklift pockets
• Supersilenced
• Ready for connection to automatic transfer unit EAS (AMF + ATS)
• Meets EC directives for noise and safety
POWER RATINGS
*
Stand-By three-phase power (LTP)
51 kVA (40.8 kW) / 400V / 73.6 A
* PRP three-phase power 46 kVA (36.8 kW) / 400V / 66.4 A
* PRP single-phase power 17 kVA / 230V / 73.9 A
* COP power /
Frequency 50 Hz
Cos j 0.8
4 STROKE, TURBOCHARGED
Model PERKINS 1103A-33TG1
Cylinders / Displacement 3 / 3300 cm³ (3.3 lt.)
Bore / Stroke 105 / 127 (mm)
Compression ratio 17.25 : 1
* Stand-By net power 45.6 kWm (62 hp)
* PRP net power 41.3 kWm (56.2 hp )
* COP net power /
BMEP (Brake Mean Eective
Pressure : LTP - PRP)
1128 kPa - 1023 kPa
Speed governor type Mechanical
FUEL CONSUMPTION
110 % (Stand-by power) 219 g/kWh - 12 lt./h
100 % to PRP 217 g/kWh - 10.7 lt./h
75 % to PRP 220 g/kWh - 8.2 lt./h
50 % to PRP 264 g/kWh - 5.7 lt./h
COOLING SYSTEM
Total system cap. - only engine 10,2 lt - 4,4 lt.
Fan air flow 53 m³/min.
LUBRIFICATION SYSTEM
Total oil system capacity 8.3 lt
Oil capacity in sump 6.2 lt, ÷ 7.8 lt
Oil consumption at full load < 016 lt./h
EnginE 1500 rPm
EXHAUST SYSTEM
Maximum exhaust gas flow 7,7 m³/mim
Max. exhaust gas temp. 537 °C
Maximum back pressure 10 kPa (0,10 bar)
External diameter exhaust pipe /
ELECTRICAL SYSTEM 12 Vdc
Starter motor power 3 kW
Battery charging alternator cap. 65 A
Cold start - 10°C
With cold start aid - 25 °C
AIR FILTER Dry
Combustion air flow 3.1 m³/min.
HEAT REJECTED AT FULL LOAD
To exhaust system 35 kW - 1992 Btu/min.
To water and oil 30 kW - 1707 Btu/min
Radiated to room 8 kW - 455 Btu/min.
To charge cooler /
* Output powers according to ISO 3046-1
* Output powers according to ISO 8528-1
The images are for reference
03/16
DEFINITION
Valid declared powers up to the followings environmental conditions: temperature
25°C, altitude 100 meters above sea level)
LTP power: stand-by power: Maximum available power for use with variable loads for a
yearly number of hours limited at 500 h. No overload is admitted.
PRP power: continue power with variable loads. Maximum power for use with variable
loads for a yearly illimited nubers of hours.
COP power: continuous power with constant load. Maximum power for use with constant
loads for a yearly unlimited numbers of hours.
water
cooled
diesel single-phase
power
three-phase
power
electric