Product Card

MADE IN ITALY
Pag 4
language
GENERATING SET
GE 50 PS SX
FEATURES
Automatic voltage regulation “AVR” with three-phase sensing
Round edges for a better rain flow
Bunded base suitable to contain any liquids leakage from engine avoiding
environmental pollution
External caps for oil and water drain
Large doors for better and easy maintenance (air, oil, fuel filters replacement)
Central lifting eye
Forklift pockets
Supersilenced
Ready for connection to automatic transfer unit EAS (AMF + ATS)
Meets EC directives for noise and safety
POWER RATINGS
*
Stand-By three-phase power (LTP)
51 kVA (40.8 kW) / 400V / 73.6 A
* PRP three-phase power 46 kVA (36.8 kW) / 400V / 66.4 A
* PRP single-phase power 17 kVA / 230V / 73.9 A
* COP power /
Frequency 50 Hz
Cos j 0.8
4 STROKE, TURBOCHARGED
Model PERKINS 1103A-33TG1
Cylinders / Displacement 3 / 3300 cm³ (3.3 lt.)
Bore / Stroke 105 / 127 (mm)
Compression ratio 17.25 : 1
* Stand-By net power 45.6 kWm (62 hp)
* PRP net power 41.3 kWm (56.2 hp )
* COP net power /
BMEP (Brake Mean Eective
Pressure : LTP - PRP)
1128 kPa - 1023 kPa
Speed governor type Mechanical
FUEL CONSUMPTION
110 % (Stand-by power) 219 g/kWh - 12 lt./h
100 % to PRP 217 g/kWh - 10.7 lt./h
75 % to PRP 220 g/kWh - 8.2 lt./h
50 % to PRP 264 g/kWh - 5.7 lt./h
COOLING SYSTEM
Total system cap. - only engine 10,2 lt - 4,4 lt.
Fan air flow 53 m³/min.
LUBRIFICATION SYSTEM
Total oil system capacity 8.3 lt
Oil capacity in sump 6.2 lt, ÷ 7.8 lt
Oil consumption at full load < 016 lt./h
EnginE 1500 rPm
EXHAUST SYSTEM
Maximum exhaust gas flow 7,7 m³/mim
Max. exhaust gas temp. 537 °C
Maximum back pressure 10 kPa (0,10 bar)
External diameter exhaust pipe /
ELECTRICAL SYSTEM 12 Vdc
Starter motor power 3 kW
Battery charging alternator cap. 65 A
Cold start - 10°C
With cold start aid - 25 °C
AIR FILTER Dry
Combustion air flow 3.1 m³/min.
HEAT REJECTED AT FULL LOAD
To exhaust system 35 kW - 1992 Btu/min.
To water and oil 30 kW - 1707 Btu/min
Radiated to room 8 kW - 455 Btu/min.
To charge cooler /
* Output powers according to ISO 3046-1
* Output powers according to ISO 8528-1
The images are for reference
03/16
DEFINITION
Valid declared powers up to the followings environmental conditions: temperature
25°C, altitude 100 meters above sea level)
LTP power: stand-by power: Maximum available power for use with variable loads for a
yearly number of hours limited at 500 h. No overload is admitted.
PRP power: continue power with variable loads. Maximum power for use with variable
loads for a yearly illimited nubers of hours.
COP power: continuous power with constant load. Maximum power for use with constant
loads for a yearly unlimited numbers of hours.
water
cooled
diesel single-phase
power
three-phase
power
electric

Summary of content (3 pages)