User Manual
Mosa reserves the right to change this specifi cation without notice. For further information please contact the sales department.
GE275FZGB
05/11
[OIL] [°C] [Hi H] [FUEL] [bELt]
Diesel
Engine
Water
Cooling
Battery
24V
(2x12V)
Engine
protection
Electric
starter
Low press.
shut down
High water
shut down
Over
speed
shut down
Low fuel
shut down
Battery
charge alarm
Central
lifting eye
Rpm-meter
Hours-meter
Battery
voltmeter
Voltmeter
Frequency-
meter
Local/Remote
Start selector
Synchronous
alternator
Automatic
voltage
regulator
Circuit
breaker
Ammeter Voltmeter
phase
selector
Emergency
stop button
Siren Ready for
EAS/TCM
Fuel level
gauge
Oil pressure
gauge
Water
temperature
gauge
Factory
installation
options
Options
on request
Technical Data
GE 275 FMSX
• ELR-Earth Leakage Relay (GFI)
• Isometer (Insulation monitors)
• Voltage regulation
• Radio control
• 400 plugs
• 230 plugs
• Electrical panel with CEE sockets:1x400V 125A 3P+N+T - 1x400V 63A 3P+N+T - 1x400V 32A 3P+N+T - 1x400V 16A 3P+N+T - 2x230V 16A 2P+T
The electrical panel requires an electrical protection: ELR-Earth Leakage Relay (GFI) or Isometer (Insulation monitors)
A.C. GENERATION - 50 Hz
Three-phase synchronous alternator, self-excited, self-regulated, brushless
*Stand-by three-phase power
*PRP three-phase power
Cosϕ
Insulation class
* Output powers according to ISO 8528-1
275 kVA (220 kW) / 400 V / 397 A
250 kVA (200 kW) / 400 V / 361A
0.8
H
ENGINE
4-stroke diesel, turbocharged-air to air charge cooled, direct injection, water cooled
Model
* Stand-By net power
* PRP
net power
Cylinders/ Displacement
Speed
Fuel consumption (75% of PRP)
* Maximum output according to ISO 3046-1
FPT (IVECO) C87 TE1D
256 kW (348 HP)
232 kW (316 HP)
6 / 8.7 l (8700 cm
3
)
1500 rpm
43.2 l/h
GENERAL SPECIFICATIONS
Tank capacity
Running time (75% of PRP)
IP protection degree
Dimensions LxWxh (mm)
Dry weight
*Measured acoustic power LwA (pressure LpA)
*Guaranteed acoustic power LwA (pressure LpA)
* Acoustic power according to European Directive 2000/14/EC
510 l
11.8 h
IP 44
3750x1400x2030
3500 kg
95 dB(A) (70 dB(A) @ 7 m)
96 dB(A) (71 dB(A) @ 7 m)
AVR
MT
• PMG (Permanent Magnet Generator)
• Water heater WH
• Low level water radiator sensor
• Automatic fuel transfer pump
• Fuel tank 120l
• 3-way valve fuel system with quick connec-
tion for external fuel tank supply
Standard
equipment
GENERATING SET
GE 275 FMSX EAS
FPT (IVECO) water cooled diesel engine - 1500 rpm
Turbo aftercooled engine with electronic governor
Closed crankcase ventilation
EP6 engine protection
Three-phase synchronous alternator
Four pole circuit breaker
Oil drain pump
Bunded Base
Two central lifting eyes
Meets EEC directives for safety and noise level
rpm
EP6
• Automatic transfer unit (AMF) EAS 275 MTE-805 • Earthing kit
• Remote control TCM35
2000 / 14 / CE