User Manual

30/07/12 CJ3K70E1_EN
ENGLISH
ENGLISH
M
1.5
TECHNICAL DATA
GE 165 FSX
REV.0-12/16
GENERATOR
Stand-by three-phase power 168 kVA (134.4 kW) / 400 V / 242.5 A
PRP three-phase power 153 kVA (122.4 kW) / 400 V / 220.8 A
COP three-phase power 122 kVA (97.6 kW) / 400V / 176.3 A
Frequency 50 Hz
Cos ϕ 0.8
ALTERNATOR self-excited, self-regulated, brushless
Type three-phase, synchronous
Insulation class H
ENGINE
Make / Model FPT (IVECO) NEF67 TE1F Stage 3A
Type / Cooling system Diesel 4-Stroke / Water
Cylinder / Displacement 6/ 6700 cm³
Stand by net power 145 kW (197.2 HP)
PRP net power 131.5 kW (178.8 HP)
COP net power 105 kW (143 hp)
Speed 1500 rpm
Fuel consumption (75% of PRP) 26.5 l/h
Cooling system capacity 25.5 l
Engine oil capacity 12 l
Starter Electric
GENERAL SPECIFICATIONS
Battery 12V - 180Ah
Tank capacity 425 l
Running time (75% of PRP) 16 h
Protection IP 44
*Dimensions / max. on base Lxwxh 3750x1400x2030
*Weight on base 2700 kg
Measured acoustic power Lwa (pressure LpA) 93 dB(A) (68 dB(A) @ 7 m)
Garanteed acoustic power Lwa (pressure LpA) 94 dB(A) (69 dB(A) @ 7 m)
* Dimensions and weight are inclusive of all parts
2000 /14/CE
OUTPUT
Output powers according to ISO 8528-1 (temperature 40°C, 30% relative humidity, altitude 1000 m above sea level).
Stand-by power (LTP): emergency power. Maximum power available for use with variable loads for a number of hours/year limited to 500 h. Overloads are
not permitted.
PRP power: continuous power with variable loads. Maximum power available for use with variable loads for an unlimited number of hours/year. The average
power output during a 24 h period must not exceed 70% of the stated value.
COP power: continuous power with constant load. Maximum power available for use with constant load for an unlimited number of hours/year.
A 10% overload is permitted one out of every 12 hours.
On average, it reduces by 1% every 1000 m above sea level and by 3% for every 5°C above 40°C.
ACOUSTIC POWER LEVEL
ATTENTION: The concrete risk due to the machine depends on the conditions in which it is used. Therefore, it is up to the end-user and under his direct
responsibility to make a correct evaluation of the same risk and to adopt specic precautions (for instance, adopting a I.P.D. -Individual Protection Device)
Acoustic Noise Level (LWA) - Measure Unit dB(A): it stands for acoustic noise released in a certain delay of time. This is not submitted to the distance
of measurement.
Acoustic Pressure (Lp) - Measure Unit dB(A): it measures the pressure originated by sound waves emission. Its value changes in proportion to the
distance of measurement.
The here below table shows examples of acoustic pressure (Lp) at different distances from a machine with Acoustic Noise Level (LWA) of 95 dB(A)
Lp a 1 meter = 95 dB(A) - 8 dB(A) = 87 dB(A) Lp a 7 meters = 95 dB(A) - 25 dB(A) = 70 dB(A)
Lp a 4 meters = 95 dB(A) - 20 dB(A) = 75 dB(A) Lp a 10 meters = 95 dB(A) - 28 dB(A) = 67 dB(A)
NOTE: the symbol
2000 /14/CE
when with acoustic noise values, indicates that the device respects noise emission limits according to 2000/14/CE directive.
41