CONTROLS DESCRIPTION
REV.0-12/16
Pos. Description Function
Z2 Thermal-magnetic circuit breaker General switch for the gen-set.
It protects both gen-set and related electrical circuit from over current /short circuit.
Z9 Engine control unit AMF25 Engine control unit.
Genset stop/ start.
Handling of generator alarms.
On-screen display of alarms, measurements, operating messages.
B6 Controller power switch Turns the generator control board on and off.
X1 Remote control socket TCM35 Connection for TCM remote control or for a NO clean contact, both operating only if AMF25
in AUT.
D6 PAC (ATS) connector Connection for the PAC transfer panel. 16-pin connector.
R3 Siren Gen-set acoustic alarm.
T5 (SR) Earth leakage relay Ground fault interrupt (GFI) relay - Protection device against indirect contact for TN systems
(GE neutral to ground).
It opens the general circuit breaker, thereby interrupting the power supply to the electrical
system.
The generator stop.
The regulations on the GFI must be performed by qualied personnel.
A3 (SR) Insulation monitoring Residual current monitor (RCM) - Protection device against indirect contact for IT systems
(GE neutral not to ground).
It opens the general circuit breaker when the isolation resistance falls below the selected
threshold, thereby interrupting the power supply to the electrical system.
The generator stop.
The regulations on the RCM must be performed by qualied personnel.
E7 (SR) Voltage regulation potentiometer Output voltage regulation: about ± 5%.
S7 (SR) Plug 230V single-phase External supply for engine heater (mains).
15 (SR)
(6
sockets kit)
Output socket 1x400V 125A 3P+N+T CEE - 1x400V 63A 3P+N+T CEE -
1x400V 32A 3P+N+T CEE - 1x400V 16A 3P+N+T CEE -
1x230V 16A 2P+T CEE - 1x230V 16A 2P+T SCHUKO
Z2 (SR)
(6 sockets kit)
Thermal-magnetic circuit breaker 1x125A Curve C 4P (for 125A socket) - 1x63A Curve C 4P (for 63A socket)
N2 (SR)
(6 sockets kit)
Thermal-magnetic circuit breaker/
Ground fault interrupter
1x32A Curve C 4P - Id=0.03 (for 32A socket)
1x16A Curve C 4P - Id=0.03 (for 16A socket)
2x16A Curve C 2P - Id=0.03 (for 16A-230V socket)
L5 Emergency stop button Press for an immediate stop of the machine (only in case of emergency)