20 kVA Perkins Diesel Three Phase Generator

GE 20 YSX
M
1.5
REV.0-09/12
TECHNICAL DATA
27/09/12 84920-GB
I
GB
F
Technical data GE 20 YSX
GENERATOR
Stand-by three-phase power 20 kVA (16 kW) / 400 V / 28.9 A
PRP three-phase power 18 kVA (14.4 kW) / 400 V / 26 A
PRP single-phase power 7 kVA / 230 V / 30.4 A
Frequency 50 Hz
Cos ϕ
0.8
ALTERNATOR self-excited, self-regulated, brushless
Type three-phase, synchronous
Insulation class H
ENGINE
Make / Model YANMAR 4TNV88
Type / Cooling system Diesel 4-Stroke / water
Cylinder / Displacement 4 / 2190 cm
3
*Stand by net power 18 kW (24.5 HP)
**PRP net power 16.4 kW (22.3 HP)
Speed 1500 rpm
Fuel consumption (75% of PRP) 3.4 l/h
Engine oil capacity (max) 7.4 l
Starter Electric
GENERAL SPECIFICATIONS
Tank capacity 100 l
Running time (75% of PRP) 29.5 h
Protection IP 44
*Dimensions / max. on base Lxwxh 1835x900x1265
*Weight on base 750 Kg
Measured acoustic power Lwa (pression LpA) 89 dB(A) (64 dB(A) @ 7 m)
Garanteed acoustic power Lwa (pression LpA 89 dB(A) (64 dB(A) @ 7 m)
* Dimensions and weight are inclusive of all parts.
2000 / 14 / CE
OUTPUT
Declared power according to ISO 8528-1 (temperature 25°C, 30% relative humidity, altitude 100 m above sea level).
(*Stand-by) = maximum available power for use at variable loads for a yearly number of hours limited at 500 h. No overload is
admitted.
(**Prime power PRP) = maximum available power for use at variable loads for a yearly illimited number of hours. The average
power to be taken during a period of 24 h must not be over 80% of the PRP.
It’s admitted overload of 10% each hour every 12 h.
In an approximative way one reduces: of 1% every 100 m altitude and of 2.5% for every 5°C above 25°C.
ACOUSTIC POWER LEVEL
ATTENTION: The concrete risk due to the machine depends on the conditions in which it is used. Therefore, it is up to the end-
user and under his direct responsibility to make a correct evaluation of the same risk and to adopt specic precautions (for
instance, adopting a I.P.D. -Individual Protection Device)
Acoustic Noise Level (LwA) - Measure Unit dB(A): it stands for acoustic noise released in a certain delay of time. This is not
submitted to the distance of measurement.
Acoustic Pressure (Lp) - Measure Unit dB(A): it measures the pressure originated by sound waves emission. Its value changes
in proportion to the distance of measurement.
The here below table shows examples of acoustic pressure (Lp) at different distances from a machine with Acoustic Noise Level
(LwA) of 95 dB(A)
Lp a 1 meter = 95 dB(A) - 8 dB(A) = 87 dB(A) Lp a 7 meters = 95 dB(A) - 25 dB(A) = 70 dB(A)
Lp a 4 meters = 95 dB(A) - 20 dB(A) = 75 dB(A) Lp a 10 meters = 95 dB(A) - 28 dB(A) = 67 dB(A)
PLEASE NOTE: the symbol when with acoustic noise values, indicates that the device respects noise emission limits
according to 2000/14/CE directive.