Product Manual

USE AS A GENERATOR
M
37
© MOSA REV.0-06/99
Sockets are not self-locked: tension is avaible
immediately after starting also with no plug.
WARNING
It is strictly forbidden to connect the group
to the public mains a/o to another source of
electric power.
Connect up the machine, using proper plugs and
cables in good condition to the AC socket (15) to
draw single or three-phase power, or, by cables
with adeguate section, to the terminal board, placed
inside the derivation box (Q3).
Nominal
voltage
230V
400V
+10%
+10%
Indicative
no-load voltage
The areas, access of which is forbidden to
unqualified personel, are:
- the control switchboard (front), the exhaust of
the endothermic engine.
WARNING
Using several sockets at tha same time, the
maximum power possible is that indicated on the
data plate.
The max. continuous power of the generating set or
the load current must not be exceeded.
THERMOPROTECTION
If you overload the genset the thermoprotection will
automatically switch off.
lf the thermoprotection is released, disconnect all
the connected loads.
CLOSED OPEN
PRESS TO
RESET
At the beginning of every work, check the electric
parameters and/or the controls placed on the
front.
Make sure that the ground connection (12) is efficent
(keep to installation local rules and/or to national
laws), in order to integrate or ensure the working of
varius electric protection devices referring to the
several distribution system TT/TN/IT, operation
unnecessary for machine with isometer.
- See page M 20-21.
Check the voltmeter (N) shows the voltage three or
single-phase has to be drawn.
Reset the thermoprotection pressing the central
pole.
When reset, connect the loads again.
In case the protection should act furtherly, check:
the connections, the wires or others, and if necessary
call the Assistance Service.
AvoId to hold the central
pole of the
thermoprotection
pressed for a long time.
Otherwise, in case of
trouble, it will not click, damaging the generating
set.
GROUND FAULT INTERRUPTER (GFI)
Turn on the GFI safety-switch
(D) by pushing it upwards.
The GFI is a safety device which protects the circuit
in the event of a malfunction. In this case the switch
disconnects the three and single-phase circuit when
in any part of the electric connections a current
leakage of more than 30 mA occurs.
CT 230 SX
GE 6000 - 6500 SX/GS
GE 7000 SX/GA