6.5kva Yanmar Three Phase Bunded Diesel Generator
MADE IN ITALY
language
GENERATING SET
GE SX-6500 YDT
The images are for reference
Pag 1
01/2020
FEATURES
• Bunded base suitable to contain any liquids leakage from engine
avoiding environmental pollution
• The rounded edges of the canopy designed for rainwater drainage
away
• Engine cowling side, can be completely opened, which facilitates all
maintenance operations
• Central lifting eye
• Circuit breaker and ELCB-GFI (Ground Fault Interruptor)
• Emergency stop button
• Supersilenced
• Ready for connection to automatic transfer unit EAS
• Automatic voltage regulator
• Meets EC directives for noise and safety
POWER RATINGS
*
Stand-By three-phase power (LTP)
6.5 kVA (5.2 kW) /400V/ 9.4A
*
PRP three-phase power
5.7 kVA (4.6 kW) /400V/ 8.2A
* PRP single-phase power 3.5 kVA/kW /230V/ 15.2A
* COP single-phase power /
Frequency 50 Hz
Cos j 0.8
EnginE 3000 rPm
* Powers declared according to ISO 8528
4 STROKE, NATURAL ASPIRATED
Model YANMAR L 100 V
Stand-By net power 6.3 kWm (8.5 hp)
PRP net power 5.7 kWm (7.7 hp )
COP net power /
Cylinders / Displacement 1 / 435 cm³ (0,435 lt.)
Bore / Stroke 86 / 75 (mm)
Compression ratio 20 : 1
BMEP (Brake Mean Eective
Pressure : LTP - PRP)
/
Speed governor type Mechanical
FUEL CONSUMPTION
110 % (Stand-by power) 1.9 lt./h
100 % to PRP 1.7 lt./h
75 % to PRP 1.2 lt./h
50 % to PRP 0.8 lt./h
COOLING SYSTEM
Total system cap. - only engine /
Fan air flow /
LUBRICATION SYSTEM
Total oil system capacity /
Oil capacity in sump 1.6 lt.
Oil consumption at full load /
EXHAUST SYSTEM
Maximum exhaust gas flow /
Max. exhaust gas temp. /
Maximum back pressure 4.3 kPa (0.043 bar 440 mmH
2
O)
External diameter exhaust pipe /
ELECTRICAL SYSTEM 12 Vdc
Starter motor power 0.8 kW
Battery charging alternator cap. 15 A
Cold start - 10°C
With cold start aid /
AIR FILTER Dry
Combustion air flow /
HEAT REJECTED AT FULL LOAD
To exhaust system /
To water and oil /
Radiated to room /
To charge cooler /
E
N
G
I
N
E
S
T
A
G
E
5
air cooled diesel three-phase electric start
DEFINITION
Valid declared powers up to the followings environmental conditions: temperature
25°C, altitude 100 meters above sea level)
LTP power: stand-by power: Maximum available power for use with variable loads for a
yearly number of hours limited at 500 h. No overload is admitted.
PRP power: continue power with variable loads. Maximum power for use with variable
loads for a yearly illimited nubers of hours.
COP power: continuous power with constant load. Maximum power for use with constant
loads for a yearly unlimited numbers of hours.