Stopping the engine
SHUT-DOWN FROM FRONT PANEL
For shutdown under normal conditions, proceed as
follows:
1
. Position the LOCAL START /REMOTE START
(I6) selector on LOCAL START; (only EAS ver-
sion);
2
. cut off power to all utilities by opening the load
switch or opening the thermal-magne-
tic switch (Z2) (input lever in downward
position);
3
. allow the motor to run without any load for a few
minutes;
4.
turn the key (Q1) to the OFF posi-
tion;
OFF
ON
START
5. shut the fuel cock.
FUEL
VALVE
SHUT-DOWN FROM REMOTE
(only EAS version)
The unit can also be shut down by means of the
TCM remote control or EAS panel.
1. Check that the EAS (B3) connector is connected
to the cable from the TCM or EAS panel.
2. Verify or position the LOCAL START / REMOT
START (I6) selector on REMOTE START.
3. SHUT-DOWN with EAS
The EAS panel automatically sees to controlling
the motor shutdown cycle, including the cooling
cycle.
4. SHUT-DOWN with TCM
Follow the same shutdown procedure described
for shutdown from the front panel using the TCM
key (Q1).
EMERGENCY SHUTDOWN
To shut down the engine in an emergency situation
turn the key (Q1) to the OFF position.
+ NB.: as a safety measure the start-up key
must be entrusted to qualied personnel.
21/03/14 15921-GB
WARNING
The start-up selector (I6) LOCAL START / REMO-
TE START enables the start-up and stop controls
for the selected position.
From the REMOTE START position, the start-up
key on the front panel is completely disabled; to
stop the generator, use the controls on the TCM
or EAS panel.
!