Product Card
Table Of Contents
MADE IN ITALY
language
SYNCHRONOUS, THREE-PHASE, SELF-EXCITED, SELF-REGULATED
Continuos power (~3) 7 kVA
Stand-by power (~3) 7.7 kVA
Stand-by power (~1) 3.5 kVA
Three phase voltage 400 ÷ 415 Vac
Single phase voltage 230 ÷ 240 Vac
Frequency 50 Hz
Cos j 1
Model A.V.R. AVR-d
Voltage regulation acc. ± 1.5 %
Sustained short circuit current 3 In
Transient dip (100% load) 10 %
Recovery time /
Eciency at 100% load 81 % (400V - Cos
j 0.8)
Insulation Class H
Connection - Terminals Series - N°4
Electromagnetic compatibility (
R.F.I. suppr.)
/
Waveform distorsion - THD < 6 %
Thelephone interference - THF /
altErnator
gEnEral SPEcificationS
Fuel tank capacity 18 lt.
Running time (75% to PRP) 7.5 h
Starter battery 12 Vdc -18Ah
IP protection degree IP 23
REACTANCES
(7 KVA - 400 V)
Direct axis synchronuos - Xd /
Direct axis transient - X’d /
Subdirect axis transient - X”d /
Quadrature axis synchronuos - Xq /
Quadr. axis subtransient - X”q /
Negative sequence - X2 /
Zero sequence - X0 /
TIME CONSTANTS
Transient - T’d /
Subtransient - T”d /
Open circuit - T’do /
Armature - Ta /
Short-circuit ratio Kcc /
IP protection degree IP 23
Cooling air flow /
Coupling | Bearing Direct SAE J609b - N°1
* Acoustic power in accordance with Directive 2000/14/EC
GE SX-8000 HBT
* Measured acoustic power LwA
(pressure LpA)
91.5 dB(A) (66.5 dB(A) @ 7m)
* Guaranteed acoustic power LwA
(pressure LpA)
93 dB(A) (68 dB(A) @ 7m)
Performance class G2
• Engine start and stop key
• Low fuel warning light
• Local-Remote Start switch
• EAS connector
• Multifunction digital instrument: Voltmeter - Frequency meter - Total hour
meter - Partial hour meter (resettable)
• Earth leakage circuit breaker
• Magnetothermic switch for 400V socket
• Output sockets: 1x 400V 16A 3P + N + T CEE IP44
1x 230V 16A 2P + T CEE IP44
1x 230V 16A 2P + T Schuko
• Earth terminal (PE)
• Pull start (in case of missing battery or low battery)
• Fuel tap
control PanEl
Pag 2