8 kva Honda Three Phase Petrol Auto Start Generator GE SX-8000 HBT

17/04/2020 CB2M1011_EN
ENGLISH
ENGLISH
REV.0-04/20
M
26
STARTING
NOTE
Do not alter the primary conditions of regulation and do not
touch the sealed parts.
!
check daily
STARTING
1) Make sure the load plugs are
disconnected or that the main
switch of machine is open (lever
facing down), so as to ensure the
engine’s start-up without any loads
inserted.
4) then return it slowly
2) Open the gasoline cock
5) pull the rope hard and fast. Pull it all the way
out. Use two hands if necessary.
NOTE
All iGX engines are equipped with an automatic choke device
(AUTO CHOKE) which facilitates the start-up phase.
In this case the manual operation is not required.
!
ELECTRIC START
Start-up from front panel
1) Position the LOCAL START / REMOTE START (I6) selector
on LOCAL START (only EAS version)
2) Turn the starter key to position “ON”.
3) Turn the start-up key (Q1) to the START position, once the
engine is started up leave the key, it will reposition itself in
“ON”
4) Once the engine is started, let it turn for a few minutes before
drawing the load.
In case of unsuccessful start-up, do not insist for longer
than 5 seconds. Wait 10 seconds before attempting
another start-up.
Remote start (only EAS version)
The unit can also be started by means of the remote TCM con-
trol device, or through the EAS automatic intervention panel.
1) Position the LOCAL START / REMOTE START (I6) selector
on REMOTE START;
2) check that the emergency stop button is unblocked (where
it is assembled);
3) Connect to the EAS (B3) connector the TCM or the EAS
panel;
4) Start-up with EAS
The EAS panel automatically sees to controlling the engine’s
start-up cycle.
5) Start-up with TCM
Perform the same procedure for start-up from the front panel
using the TCM start-up key (Q1).
3) hold the starting handle properly and pull slowly
until you feel resistance
ATTENTION: Allow the start-up knob to re-enter slowly,
avoiding having it knock against the motor and thereby
damaging the start-up system.
MANUAL RECOIL FOR ELECTRIC STARTING VERSIONS
In case of lack of battery or low battery the engine can be
started manually.
After steps 1) and 2) of the STARTING paragraph, proceed
as follows:
1) position the LOCAL START / REMOTE START (I6) selector
on LOCAL START (only EAS version)
2) turn the start-up key (Q1) to the ON position.