User Manual
GE 12000 SXC/GS / AVR
GE 14000 SXC/GS / AVR
M
22
REV.0-04/14
Shutting down the motor
08/04/1435931-GB
SHUT-DOWN FROM FRONT PANEL
Forshutdownundernormalconditions,proceedas
follows:
1. Position the LOCALSTART/REMOTE START
(I6)selectoronLOCALSTART;(only EAS ver-
sion);
2. cutoffpowertoallutilitiesbyopeningtheload
switchoropeningthethermal-magne-
ticswitch(Z2)(inputleverindownward
position);
3. Turnandpushtheacceleratorlever(16)inmini-
mumposition;
4. allowthemotortorunwithoutanyloadforafew
minutes;
5. turnthekey(Q1)totheOFFposition.
+ NB.: as a safety measure the start-up key
must be entrusted to qualied personnel.
OFF
ON
START
The start-up selector (I6) LOCAL START / REMO-
TE START enables the start-up and stop controls
for the selected position.
From the REMOTE START position, the start-up
key on the front panel is completely disabled; to
stop the generator, use the controls on the TCM
or EAS panel.
WARNING
!
SHUT-DOWN FROM REMOTE
(onlyEASversion)
Theunitcanalsobeshutdownbymeansofthe
TCMremotecontrolorEASpanel.
1. CheckthattheEAS(B3)connectorisconnected
tothecablefromtheTCMorEASpanel.
2. VerifyorpositiontheLOCALSTART/REMOT
START(I6)selectoronREMOTESTART.
3. SHUT-DOWN with EAS
TheEASpanelautomaticallyseestocontrolling
themotorshutdowncycle,includingthecooling
cycle.
4. SHUT-DOWN with TCM
Followthesameshutdownproceduredescribed
forshutdownfromthefrontpanelusingtheTCM
key(Q1).
EMERGENCY SHUTDOWN
Turnthekey(Q1)totheOFFposition.